Securitron DK-12 User Manual

Page 3

Advertising
background image

PN# 500-24010

Page 3

Rev. C, 04/11

Double Break Wiring For Free Egress (SPDT):
 Connect DC supply to ‘AC/DC+’ and ‘AC/DC-’

terminals.

 Connect ‘AC/DC+’ terminal to the common terminal of

the SPDT switch.

 Connect the normally closed contact of the SPDT switch

to the ‘COM’ terminal.

 Connect the normally open contact of the SPDT switch

to the ‘REX” terminal through resistor (R).

 Connect ‘NC’ terminal to the positive lead of lock.

 Connect other lead of lock to the ‘AC/DC-’ terminal.


NOTE: Resistor (R) is 3300 ohms, ½ watt.


5. WIRING WITH SECUTITRON’S TOUCH SENSE BAR AND MAGNALOCK

Touch Sense Bar and Magnalock Wiring:
 Connect supply to ‘AC/DC+’ and ‘AC/DC-’ terminals.

 Connect ‘AC/DC+’ terminal to the red and white wires

of the Touch Sense Bar.

 Connect ‘AC/DC-’ terminal to the black wires of both

the Touch Sense Bar and the Magnalock.

 Connect ‘NC’ terminal to the red lead of the Magnalock.

 Connect ‘COM’ terminal to the green lead of the Touch

Sense Bar.


6. FEEDBACK AND ENTRY OVERVIEW
The DK-12 comes with indictor lights above the keypad; left-hand side green, center yellow, and
right-hand side red. These three indictor lights, and the backlight, provide feedback during
operation. Note that the green and red LEDs could be reversed thru programming.

INDICATOR ACTION

MEANING

Red Light

Single Flash

 While in programming mode an error was made during

program entry; or

 The program entry was correct but the DK-12 can not accept

the programming, for example a code was trying to be set
that is a subset of another code; or

 A 5 second timeout occurred at any time during a

programming step.

Red Light

Double Flash

 While in programming mode a confirmation that a valid

program entry was made; or

 During normal operation the DK-12 was put into or taken out

of lockout mode.

Red Light

Continuous

Flashing

During normal operation the relay is energized while the DK-12
is in relay timer mode; flashes once per second.

Red Light

Continuously

On

 While in normal operation the DK-12 is in passage mode; or

 The DK-12 is in toggle mode and the relay is energized; or

 The REX input is being held active.

Yellow Light

Continuous

Flashing

 While in programming mode the light will flash once per

second; or

 While the ‘PCR’ jumper is in the ‘ON’ position the light will

flash once per second.

Yellow Light

Continuously

On

While in normal operation this indicates that there are no codes

in memory.

Green Light

Single Flash

Key press detected.

1 2 3 4 5 6 7

DK-12

Back Side

Power Supply

Magnalock

Red

Black

Touch

Sense Bar

Black

Red

White

Green

1 2 3 4 5 6 7

DK-12

Back Side

DC Power Supply

Fail-Safe DC

Electric Lock

NO

NC

C

SPDT Switch

R