Gillette Generators SPP-180 User Manual

Page 18

Advertising
background image

PAGE 18

NOTE: For air
temperatures
below 32º F (0º
C), it is highly
recommended to
replace oil with a
synthetic oil, API
SJ/CF

5W-30W.

This allows for
easier

engine

starting and better dry fuel engine performance
during cold weather.

Add necessary oil to bring level to “upper limit” on
dipstick, replace dipstick and filler cap.

2) Check radiator fluid level on generator sets that
are liquid cooled. The radiator was factory filled with
a 50% mixture of water and anti-freeze. Fill radiator
to full level only if level is low. DO NOT OVERFILL
ABOVE FULL LEVEL.

3) Become familiar with gen-set control panel (see
page 11) before actual operation takes place. Keep
the “MODE SELECTOR” switch located on the control
panel in (OFF/RESET) position at all times, while
connections, battery installation, or any other
installations take place. The “MODE SELECTOR”
switch, placed in “STANDBY” or “TEST MODE”
position during this time, may cause unwanted
engine crank action. However, if the 20 amp
controller fuse is removed, and the controller “MODE
SWITCH” is kept in the “OFF/RESET” position, the
engine cannot start up. Keep controller in this
position until “Initial Start-Up” test is performed.

The “MODE SELECTOR SWITCH” is a 3 position
device,

referred

to,

as

a

“TEST-OFF/RESET-

STANDBY” switch, as shown on page 11.

“STANDBY” position is the normal operation position.
When a utility power outage is sensed, the control
system will automatically start the generator. After a
few seconds, the generator will reach full operating
speed and connect “KLEEN-POWER

®

” generator

power to the automatic transfer switch. When utility
power returns, the control system automatically
connects utility power back to the automatic transfer
switch, allowing the generator to continue to run for a
few minutes for a “cool down” at no load, shuts down
and is on guard for the next utility power failure.

“OFF/RESET” switch position will turn off a running
generator, takes the control system out of the
automatic start/stop mode and resets any fault
condition. This is important: If any fault condition
happens (low oil, high temperature, etc), this
switch must be turned to “OFF/RESET” while
repairs are made. If the controller is not “RESET”
the automatic operation cannot function. The
generator will not exercise in this position.

“TEST” position will start the engine, but will not
disconnect utility power from the transfer switch. This
position is used for testing the generator after
maintenance or repairs, or viewing the (8) point
diagnostic functions. See page 11 for Control Panel
view.

4) Become familiar with the “Sentry-Pro control
Panel” and its functions. Especially note the (8)
annunciators and their specific actions (LED actions
that have flashing or steady on lights) (see page 11).
Consult optional equipment items, if a remote (8)
point annunciator is required at a more convenient
viewing location.

ADDITIONAL HIGHLIGHTS OF

SOLID STATE, DIGITAL

MICROPROCESSOR CONTROLLER

With (8) Point Diagnostic Panel

(See page 11)

Time Delay to Engine Start (TDES): A time delay
period of up to 10 seconds should exist from
initial power outage, to actual engine start. This
avoids false starts on intermittent power losses.
The "Engine Running" LED will constantly flash
during this period. The generator is shipped with
this TDES set to 0 seconds because the TDES is
usually controlled by the transfer switch. This 0
second delay may be optionally enabled to a 10
second delay if the function is not provided by the
transfer switch or no transfer switch is available.

Cool Down: When utility power returns, load is
switched back to utility power, and engine
continues to run for (2) minutes, unloaded to cool
down engine and generator. This (2) minute cool
down delay may be optionally disabled, if
required.

LED Test: All LED lights automatically flash (3)
times upon switching into “Standby” mode. This
function acts as a LED light test.

When fault condition occurs, repair the problem
and turn the mode selector switch to “off/reset”
for 15 seconds to clear all past memories, and
reset the controller.

Controller Memory Clear Time: If one was to turn
controller off, then immediately turn it back on
without waiting 15 seconds or more, the controller
still thinks it’s in the running mode, and sees the
gen-set, as stopped. This would be indicated by
a flashing “Over Speed” LED. When resetting
controller, always allow 15 seconds, before it is
put into “Standby” mode, to avoid this problem.

In some applications, the gen-set is used with an
inverter rather than utility power. Inverters can
produce harmonics, that disrupts the entire