Hochiki CHQ-SZM/M(SCI) User Manual

Page 3

Advertising
background image

Hochiki Europe (UK) Ltd

Page 3

2-3-0-778/ISS8/DEC11

Standard EOL Options for CHQ-DZM

EOL Option Type

Part

Description

OPTION 1
Zener End of line device
(Zone)

TE-RH-E
Hochiki Part No 2-1-1-016

(Iz=1-mA, T=30ms, Vz=22.7 to 24.3 V)
L terminal connects to +Zone
C Terminal connects to -Zone

OPTION 2
Active End Of Line Module
(Zone)
Active End Of Line

in conjunction with

Capacitor (Zone)

LCMU (6K8)
Hochiki Part No 1270070-00
(SUPPLIED SEPARATELY)




47 µF Capacitor
Hochiki Part No (2-2-7-031)

Active EOL - Line Continuity Monitoring Unit for Schottky bases (See Fig 6)
Pink lead connects to +Zone
Black lead connects to –Zone




47 µF ±20% 35 V
Fitted directly into Zone terminals (see Fig 6)

OPTION 3
Resistive EOL (Zone)

6K8 resistor (2-2-5-1015)

6K8 ± 5% 0.4 W

Monitored input EOL

10 KΩ resistor (2-2-5-806)

10 KΩ ± 5% 0.4W

CHQ-SZM SINGLE ZONE MONITOR is a loop-powered module that provides a
single fully monitored input for the connection of up to six Hochiki conventional
smoke or heat detectors, OR one Hochiki beam detector, or any number of
conventional call points, the unit also contains an output for remote fire
indication.

Note: The end of line device
(EOL) is supplied with the unit –
do NOT discard in error!

The

EOL device MUST be fitted at the
last detector on the zone, note the
polarity.

Order codes

CHQ-SZM(SCI) / CHQ-SZM/M(SCI) / CHQ-SZM/DIN(SCI) *

1

Transmission method

Digital communication using ESP

Loop:-Operating voltage

17 - 41 VDC

Quiescent current

260

A

Current consumption whilst polling

22 mA

 20 %

Current in short-circuit

8 mA

Maximum short-circuit current (Loop)

1 A

E.O.L device

TE-RH-E (polarity conscious)

Zone voltage

15.3 V - 17.1 V

Zone resistance

50

 (Max)

Zone capacitance

0.3

F (Max)

Detectors per zone

DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 6 max
SPB-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other
detectors, DRD-E – 3 max, Conventional Call Points – No limit

Weight (g) &
Dimensions (mm)

CHQ-SZM(SCI)
CHQ-SZM/M(SCI)

328

L157 x W127 x D35 (CHQ Module plus Lid)
D79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)
L108 x W119 x D24 (CHQ DIN Module)

CHQ-SZM/DIN(SCI) 114

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

* Fire alarm control panel compatibility required for these products. See AP0127 for short-circuit isolator specifications.

This module does not support any line continuity options; therefore, if Manual Call Points are to be interfaced then these should be
connected first.

Fig 7

Fig 8

Fig 6