Hochiki FB-1 User Manual

Page 15

Advertising
background image

ESP FIREbeam – Installation Manual

Page 15 of 19

 2011 Hochiki Europe (UK) Ltd

2-3-0-1340/ISS2/DEC11

3.3.3

Mode Change

Here we can make changes to how the beam behaves. Press

enter

to

go into the ‘Mode Change’ menu and access the sub menus.

Threshold

- use the

right

and

left

keys to increase or decrease

the beams sensitivity. It is factory set at 35% (meaning the received
signal has to drop by 35% to trigger the fire relay. This sensitivity can be
adjusted between 25% (sensitive) and 50% (less sensitive). Press

enter

to return to ‘Mode Change’ or

down

to go to ‘Time to Fire’.

Time to Fire

- you can adjust how long the beam has to be in fire

before the fire relay is triggered. This is factory set at 10s, you may want
to increase this if there is something that may momentarily obscure the
beam path (birds/forklift truck etc). This can be adjusted between 2 and
30 seconds by using the

right

and

left

keys. Press

enter

to

return to ‘Mode Change’ or

down

to go to ‘Time to Fault’.

Time to Fault

- you can adjust the time to fault between 2 and 60

seconds (factory set at 10 seconds). For a beam to go into fault the
beam path must be totally blocked within ONE second. By using the

right

and

left

keys. Press

enter

to return to ‘Mode Change’ or

down

to go to ‘Auto Reset’).

Auto Reset

- the beam is factory set to auto reset when the received

signal raises above the fire threshold hysteresis. This can be set to
latching if your system requires this. Change by using the

right

and

left

keys. Press

enter

to return to ‘Mode Change’ or

down

to go to

‘Align On/Off’.

Align On/Off

- you may want to turn the auto alignment function off, for

example, in an environment that often gets filled with welding smoke, the
auto align function kicks in when the received signal drops below 90%,
the point that the beam automatically checks for building movement. The
beam will try to align through the smoke which could be a problem if it is
unable to see the edges of the reflector. Use the

right

and

left

keys

to turn off and on. When turning this function off extra care should be
taken to ensure that the beam head is on a sturdy fixing, in other words,
a brick wall or major structural steel. Auto alignment will still function in
commissioning. Press

enter

to return to ‘Mode Change’ or

down

to go

to ‘Align Time’.

Align Time

- this is factory set to 4hrs, you can adjust this, by using the

right

and

left

keys, between 0 to 12 hours depending on your

environment. Press

enter

to return to ‘Mode Change’ or

down

to go to

‘Green Flashing Light On/Off’.

Green Flashing Light On/Off

- you can turn the green flashing LED,

located on the head and controller, on or off using the

right

and

left

keys. This is a useful way of identifying the beam head you are working
with. Press

enter

to return to ‘Mode Change’ or

down

to go to ‘Phase’.

Advertising