Specifications and name of each part, 1 general specifications – IAI America RCM-GW-CC User Manual

Page 11

Advertising
background image

7

2. Specifications and name of each part

2.1 General specifications

Item Specification

Power supply

24V DC ±10%

Consuming current

300mA max.

Communications standard

CC-Link Ver1.10 (*1)

Communications speed

10M/5M/2.5M/625k/156kbps (Selection with rotary switch)

Communications system

Broadcast polling system

Synchronization system

Frame synchronization system

Encoding system

NRZI

Transmission path format

Bus format (EIA RS485 conformance)

Transmission format

HDLC conformance

Error control system

CRC (X

16

+ X

12

+ X

5

+ 1)

Number of occupied stations

Remote device station 4 stations

Communications speed (bps)

10M

5M 2.5M 625k 156K

Communications cable length
(*2)

Overall cable length (m)

100

160 400 900 1200

CC-Link specification

Communication cable

CC-Link dedicated cable

Transmission path configuration

Our dedicated multi-drop difference communication

Communications system

Half-duplex

Synchronization system

Asynchronous type

Transmission path format

Equivalent to EIA RS485 2-wire type

Communication speed

30.4kbps

Error control system

No parity bit, CRC (*3)

Communication cable length

Total cable length 100m or shorter

Connecting unit number

Maximum 3/7/14/16 axes (depending on operation mode)

SIO communication specification

Communication cable

Two-paired twist-pair shielded cable
(Recommended brand: Taiyo Electric Wire & Cable
HK-SB/20276×L 2P×AWG22)

Operating ambient temperature

0 - 40°C

Operating ambient humidity

85%RH or less (non-condensing)

Operating atmosphere

Not subject to corrosive gas, flammable gas, oil mist, powdered dust

Storage temperature

-10 - 65°C

Storage humidity

90%RH or less (non-condensing)

Environment

al

Vibration resistance

4.9m/s

2

(0.5G)

Protection class

IP20

Weight

480g or less

(*1) Certification has been acquired
(*2) For T branch communication, refer to the Operation Manuals for the master unit and PLC to be

mounted.

(*3) CRC: Cyclic Redundancy Check

Data error detecting method which is mostly used for synchronizing transmission