KB Electronics KBPC-240D User Manual

Page 15

Advertising
background image

12

FIG. 11 – REMOTE

POTENTIOMETER

FIG. 12 – ANALOG VOLTAGE

FIG. 13 – REMOTE START/STOP SWITCH

FIG. 14 – INHIBIT CIRCUIT

Note: If the tach voltage is connected backwards, the control will drive the motor

at full speed only. Note: If the Forward-Brake-Reverse switch is used, provision

must be made to reverse the polarity of the tach-generator leads when the control

is switched to "Reverse."

Warning! To avoid erratic operation do not bundle AC Line and motor wires with

potentiometer, voltage following, enable, inhibit or other signal wiring. Use

shielded cables on all signal wiring over 12" (30 cm) – Do not ground shield.

F. Main Potentiometer – The control is supplied with

the main potentiometer prewired. However, the

control can also be operated from a remote

potentiometer, or from an Isolated analog voltage

for voltage following. To operate from an external

source remove white, orange and violet

potentiometer leads from terminals P1, P2 and P3.

The leads may be taped and left in the control. The

potentiometer itself may be removed, if a watertight seal is used to cover the hole in the

front cover.
1. Remote Potentiometer – Connect remote potentiometer wires to terminals P1, P2 and

P3, so that the "high" side of the potentiometer connects to P3, the "wiper" to P2 and

the "low" side to P1. (See figure 11.)

2. Analog Input – An isolated 0-5 or 0-10VDC

analog voltage can also be used to drive the

control. Note: If an isolated signal voltage is

not available, an optional signal isolator can

be installed (Model KBSI-240D, P/N 9431,

see figure 17, p. 20 for signal isolator wiring

diagrams). Connect the isolated input voltage

to terminal P2 (+) and P1 (–). (See fig. 12)

Note: Be sure jumper J7 corresponds to proper range of input voltage 0-10 or 0-

5VDC. When the potentiometer is disconnected from P1, P2 and P3 to connect an

analog input signal, the MIN trimpot will have to be adjusted clockwise to achieve a

0

+

output voltage.

G. Remote Start/Stop Switch – A remote

Start/Stop Switch can be installed by

removing the wires from the "Start,"

"Com" and "Stop" terminals, and

reconnecting them to a remote switch.

(See fig. 13.) Note: To eliminate

Start/Stop function, join the "Start" &

"Com" Quick Connect terminals with a jumper.

H. Inhibit – The control can be

electronically stopped and started with

the Inhibit circuit. To "Stop" the

control, Terminals I1 & I2 must be

joined via a contact. The control can

be restarted by opening the contact.

Note: The Inhibit should not be used as a safety disconnect. Use only the AC Line

for that purpose. (See fig. 14.) Note: The Inhibit Circuit is not isolated. Do not common

or ground inhibit leads.

I. Enable – The control can also be started and stopped with an Enable circuit (the Enable

circuit functions opposite to that of the inhibit circuit; INHIBIT: open to start-close to stop,

ENABLE: open to stop-close to start). The Enable function is established by wiring a

contact in series with the violet potentiometer lead connected to terminal P3. (See fig. 15

on page 13.) The Enable circuit is not isolated. Do not common or ground wiring. Note:

The MIN speed trimpot must not be set higher then 70% CW rotation (approx. 2:00 o'clock

position) or Enable will not function.

Advertising
This manual is related to the following products: