KB Electronics KBMG-212D User Manual
Page 23

FIG. 14 – VOLTAGE
FOLLOWING CONNECTION
FIG. 13 – MECHANICAL SPECIFICATIONS (INCHES / [mm])
21
F. Voltage Following – An isolated
analog voltage can be used in lieu
of main speed potentiometer.
Connect signal to terminals “SIG"
and “COM.” Note: Terminal “COM"
is common. A positive signal to
terminal “SIG” will produce a
positive output to motor.
A negative signal to terminal
“SIG" will produce a negative
output. A 0 to ±10VDC is required
to operate control from 0 ± full
output. Note: Jumper J4 must be
in the “10V” position.
Note: An isolated signal voltage must be used or
catastrophic failure can result. (A bipolar signal isolator, model SIMG [KB P/N
8832], is available as an option from your distributor.)
G. Enable Start/Stop Circuits – The KBMG-212D contains a 2-wire stop circuit
(Enable), which is used to electronically bring the motor to a “stop.” An isolated
single contact closure is required. If an isolated contact is not available, it may be
necessary to use an isolation relay.
*Note: If 2-wire start/stop circuit is not used, a jumper must be wired to EN
and COM or control will not operate.
WARNING! Do not use Start/Stop or Enable functions as a safety
disconnect. Use only an AC line disconnect for that purpose.
22
4.300
[109.22]
0.485
[12.32]
0.750
[19.05]
2.500
[63.50]
Jumper*
VDC
0 – ±10V
0.190
[4.83]
0.950
[24.13]
1.75
[44.45]
3.800
[96.52]
0.250
[6.35]
3.625
[92.08]