KB Electronics KBRG-255 User Manual

Page 10

Advertising
background image

6

For example, if the tach is 25V/KRPM and the motor speed is 3,600 RPM, use the "50V"

J4 position. For other tach-generator voltages and motor speeds, an external resistor

(RT) may be used as follows.

i. Install resistor in series with either tach-generator lead.

ii. Place J4 in "7V" position.

iii. The value of RT is calculated as follows.

RT = [(5.4 x Vt x S) - 68,000]

VT = Tach voltage in volts/1000 RPM

Choose the closest standard 1/2 watt

S = Base Speed of motor in RPM

resistor value to the calculated value

B. J5 - Feedback Type – The KBRG-255 can be operated in either armature feedback

"AFB" or tach-generator feedback "TFB." Armature feedback provides adequate load

regulation for most applications. For very precise performance, tach-generator feedback

"TFB" should be used. (Note: If tach feedback is desired, an external DC tach-generator

must be used and connected as per instructions.) (See section V J, p. 10 for tach-

generator wiring.) (Note: The IR Comp trimpot must be set to the minimum setting [CCW]

for tach feedback.)

C. J6 - Current Limit (CL) Mode – The KBRG-255 contains electronic current limiting that

limits the maximum DC current to the motor. Two modes of current limit are provided:
1. Timed Current Limit "TCL" – Turns the drive off after a preset time. (The time period

is adjustable with the TCL trimpot from 1-15 seconds and is factory set for

approximately 5 seconds.) In order for the Timed CL feature to operate, the

Start/Stop circuit must be wired. To restart drive after it has "timed out," the Start

button must be pressed.
Application Note: The “TCL” feature cannot be used in either torque mode, since

nuisance tripping will occur.

2. Non-Timed Current Limit "NTCL" – In this mode, the drive will reach preset Current

Limit during overload and stay at that level until drive is turned "off" or fuse blows. If

Non-Timed CL is desired, move jumper J6 from the factory set "TCL" position to the

"NTCL" position.

IV. MOUNTING.

Mount the KBRG-255 in a vertical position (connection terminals in down or up position) on

a flat surface free of moisture, metal chips, or corrosive atmosphere. (Note: If drive is

mounted in other than a vertical position, decrease maximum allowable ambient temperature

by 10 ºC.) (See Mechanical Specification fig. 5, p. 8.) A 5K ohm Remote Speed potentiometer

is provided with each control. Install potentiometer using hardware provided. Be sure to

install insulating disk between potentiometer and inside of front panel.

Enclosure – When mounting the KBRG-255 in an enclosure, it must be large enough to allow

for proper heat dissipation. A 18"x24"x36" enclosure is suitable for the KBRG-255 at full

rating. Smaller enclosures may be used if full rating is not required.

V.

WIRING.

Warning! Read Safety Warning before attempting to use this control.

Warning! To avoid erratic operation do not bundle AC Line and motor wires with

potentiometer, voltage following, enable, inhibit or other signal wiring. Use shielded

cables on all signal wiring over 12" (30 cm) – Do not ground shield.

Wire control in accordance with National Electric Code requirements and other local codes

that apply. Be sure to fuse each conductor which is not at ground potential (do not fuse

neutral or grounded conductors). (See section VI, p. 10, for fuse information.) Wire control

in accordance with connection diagrams (see figs. 3,4,6 & 7A-E). A separate AC line switch

or contactor must be wired as a disconnect switch to control so that contacts open each

ungrounded conductor. See table 4 p. 7 for terminal block wiring information.

Advertising