KB Electronics KBPW-240D User Manual

Page 14

Advertising
background image

NTCL (Non-Timed Current Limit) – When jumper J3 is set to “NTCL” position, the con-
trol will not go into “STOP” after it is in overload.

Note: TCL trimpot will have no affect when jumper J3 is in “NTCL” position.

D. DC Tach-Generator Voltage Selection (J1 and J4) – For a tach-generator wired to TB3,

set jumper J1 to “T” position. See Figure 16. Jumper J4 is factory set to “7V” position for
7 Volt per 1000 RPM tach-generators wired to TB3. For a 50 Volt per 1000 RPM tach-
generator, set jumper J4 to “50V” position.

Note: When using a tach-generator, the IR trimpot should be set fully counterclockwise.

Note: The tach-generator input is designed for 7 Volt or 50 Volt per 1000 RPM tach-
generators used with 1800 RPM motors. For tach-generators other than 7 Volt or 50 Volt
per 1000 RPM or for motors other than 1800 RPM, an external 1/2 watt resistor (R

T

) must

be used. Install R

T

in series with the tach-generator as shown in Figure 17. Jumper J4

must be set to “7V” position.

The value of R

T

in Ω can be calculated using the following formula:

R

T

= (1.46 x V

T

x S) - 19,000

Where V

T

is the tach-generator voltage (in Volts per 1000 RPM) and S is the base speed

of the motor (in RPM).

Example:

E. Run Relay Output Mode Selection (J5) –

Jumper J5 is factory set to “NO” position for nor-
mally open relay output at TB4. For normally
closed relay output, set jumper J5 to “NC” posi-
tion. See Figure 18, on page 12.

V.

MOUNTING INSTRUCTIONS

Warning! The KBPW-240D is not designed to
be used in an explosion-proof application.

It is recommended that the control be mounted verti-
cally on a flat surface with adequate ventilation.
Leave enough room below the control to allow for AC
line, motor connections, and any other wiring.
Although the control is designed for outdoor and
washdown use, care should be taken to avoid extreme hazardous locations where physical
damage can occur. If the control is mounted in a closed, unventilated location, allow enough
room for proper heat dissipation. If operating the control at full rating, a minimum enclosure
size of 12”W x 24”H x 12”D is required. See Figure 2, on page 5.

11

Suppose you have a 20 Volt per 1000 RPM tach-generator with a 3600 RPM motor:

R

T

= (1.46 X 20 X 3600) - 19000 = 86120Ω.

Choose the closest 1/2W resistor value, which is 82000Ω (82kΩ) or 91000Ω (91kΩ).
Readjustment of the MAX trimpot may be necessary to achieve the desired maximum
output voltage.

50V

7V

7V 50V

90V

180V

T

J1

J4

J4

90V

J1

180V

T

J1 Set for 90 Volt Motors

(Factory Setting)

J4 Set for 7V per 1000RPM

Tach-Generator Input

(Factory Setting)

J4 Set for 50V per 1000RPM

Tach-Generator Input

J1 Set for

Tach-Generator Input

Jumper J1 Settings

Jumper J4 Settings

FIGURE 16 – DC TACH-GENERATOR VOLTAGE SELECTION

T

G

R

DC TACH-GENERATOR

+

-

TACH

RELAY

P1

K1

K2

T+

T-

TB3

TB4

P2

P3

FIGURE 17 – DC TACH-GENERATOR

WITH ADDITION OF R

T

!