Testing does not affect normal operation of alarm system when
connected to release device/control panel. Testing of the release
device is independent of, and shall in no way be interpreted as an
alternative method of, testing of a central fire alarm system,
motorized operator and/or any other system component
employed on the fire door or counter fire door installation.
Complete testing and normal operation can only be accomplished
with power applied to device. Verify options ordered and installed
with device.

TEST RELEASE DEVICE AND DOOR OPERATOR

AUTOMATIC DOOR CLOSURE TESTS
(MOTORIZED DOORS ONLY)

Release Device Test Button – with AC Power

1. Clear fire door opening and prohibit traffic through door

opening while testing.

2. Turn on power to release device. The Red power LED will light

on the release device and the battery trouble sounder will
begin to beep.

3. Connect battery leads using the included battery interconnect

wire and the release device battery wires (Figure 10). Green
LED will light indicating battery is connected and charging.

4. Turn on power to motor. Motor sense disable Yellow LED will

light indicating power is present at motor control secondary.

5. Fully open door.

6. Depress and continue to hold the test button on the release

device. The optional annunciator (or voice board) will turn on
and after the preset delay the door will begin to close.
Annunciator will turn off when door reaches the auxiliary
close limit.

7. Release test button. The test is complete.

8. Depress “Open” button on door control to raise door to fully

open position.

To prevent possible SERIOUS INJURY or DEATH:
• Clear fire door opening and prohibit traffic through door

opening while testing.

• DO NOT install this device on a motorized door without an

electric safety edge.

• Test every 90 days to assure proper operation of release

device.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

WARNING

CAUTION

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

Figure 10

Red Wire to Red Terminal

Test Button

Battery Interconnect Wire
Battery 1 Red to Battery 2 Black

Use two 12V 4.5H sealed
lead acid batteries in series.
Maximum charge current 1A.
Replace batteries every 2 years.

Black Wire to Black Terminal