Agency requirements, Preparation – LiftMaster LM21AFCB Advance Fire Control Release Device User Manual

Page 3

Advertising
background image

I N T R O D U C T I O N

3

AGENCY REQUIREMENTS

Installation and testing to factory specifications shall be
performed by factory authorized personnel for proper operation in
accordance with the latest National Fire Protection Association
(NFPA), Underwriters Laboratories (UL), National Electrical Code
(NEC), local, state, county, district and/or other applicable
building and fire standards, guidelines, regulations and codes
including, but not limited to, all appendices and amendments and
the requirements of the local authority having jurisdiction (AHJ).

SPECIFICATIONS

To prevent possible SERIOUS INJURY or DEATH:
• DO NOT install this device on a motorized door without an

electric safety edge.

• DO NOT use this device without fuse links installed.
• Test every 90 days to assure proper operation of release

device.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

WARNING

CAUTION

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

VOLTAGE RATING:

120Vac, 60Hz

STANDBY CURRENT:

.20A

ALARM CURRENT:

.25A

BATTERY RATING:

12V 4.5AH Sealed Lead Acid
Batteries (2), Maximum charge
current .150Amps

BATTERY STANDBY TIME: LM21AFCB, 48 hours

LM21AFCBVB, 36 hours

INITIATING DEVICE:

Maximum line impedance 20 ohm;
Maximum current not to exceed
.010A.; Maximum voltage 24Vdc

LOAD RATING:

Support and Release 40 lbs. Max.

PHYSICAL DIMENSIONS:

10" x 10" x 5" (h x w x d)

PREPARATION

It is imperative that the wall or mounting surface provide
adequate support for the release device.

Refer to the door manufacturer’s recommendations for use of this
product with specific door being utilized. Use only hardware
approved or recognized by the appropriate testing and listing
agencies in conjunction with the installation of this product.

Additional items may be required to complete the installation:

• Concrete anchors or fasteners

• Sash chain or 1/16 cable

• Eyebolts-hook

• Fuse links

• Turnbuckles

• Smoke detectors (up to 4 may be installed with this device)

Refer to NFPA 72 and NFPA 80 for instructions concerning proper
placement and detection coverage. End-of-line devices shall be
installed for supervision of electrical power to 4-wire smoke
detector. When using 4-wire smoke detectors with this device,
electrical supervision must be provided by means of a UL/ULC
listed end-of-line relay.

ELECTRICAL SPECIFICATIONS

MECHANICAL SPECIFICATIONS

FUSES:

2A @ 250V, 2AG Slo-Blo Type

MOTOR CONTROL SENSE: Input Voltage 24Vac/dc

Typical +15% / –10%;
Input Current not to exceed .004A

AUXILIARY POWER:

24Vdc @ .75A Maximum

COMMON ALARM RELAY:

.

5A 125Vac 60Hz

(MAX. CONTACT RATING)

1A 24Vdc Resistive

WEIGHT:

Approximately 18 lbs.

(INCLUDING BATTERIES)

Electric Safety Edge

(Motorized

Doors

Only)

Smoke
Detector

Release
Device

Turnbuckle

Annunciator

Test/Reset
Switch

Fire Door

Chain
End Link

Fuse Links

Eyebolt