CONNECTIONS FROM DEVICE TO THE OPERATOR

NOTE: For low voltage wiring #18 AWG is recommended.

OPERATOR CONNECTIONS

1. Connect terminals 11 and 12 from the release device to the

transformer secondary in the door operator. The required
voltage should be 24-30Vac.

NOTE: This connection must be made in order to avoid a
mechanical release in alarm conditions when the door is not
closed (Figure 2).

2. Connect release device to auxiliary limit switches on the

operator. These are required and must be provided by the
door operator manufacturer.

Auxiliary Closed Limit Switch (Figure 1):
Connect a wire from the common and N/O of the auxiliary limit
switch to terminals 13 and 14 on the release device. This input
will not allow a mechanical release if the auxiliary close limit is
activated. This circuit also turns off annunciators when the
auxiliary close limit is activated.

6

W I R I N G

To prevent DAMAGE to the circuit board, auxiliary limit switches
MUST be provided as dry contacts and may not be used in
conjunction with the simultaneous switching of a motor control
or ANY other voltage through the same contacts. Connections of

this type will result in immediate damage to the release device.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

CAUTION

CAUTION

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

Auxiliary Open Limit Switch (Figure 1):
Connect a wire from the common and N/O of the auxiliary limit
switch to terminals 14 and 15 on the release device. A
connection to an auxiliary up limit switch is required for
3-cycle obstruction count feature. Adjust the auxiliary open
limit to activate just before the operators open limit is activated.

3. Connect wires from terminals 7, 8, 9, and 10 to the door

operator terminals that are used for 3-button station (for use
with N/O ‘Close’ switch, N/O ‘Open’ switch and N/C ‘Stop’
switch). The close relay output latches to initiate a door closure
through the operator after the factory set delay.

Figure 1

Figure 2

Auxiliary Limit Switches

Auxiliary Close Limit (N.O.)

Auxiliary Open Limit (N.O.)

Common

LMEOLRES-2-2

4-Wire Smoke
Detector Wiring

End of Line Relay

24 Vdc
4-Wire Smoke
Detector Wiring
(4 Detector
Maximum)

2.2

kOhm

Smoke
Detector

Smoke
Detector

Additional Dry Contact

2.2
kOhm

Safety Edge

Safety Edge Common

Open B

u

tton Inp

u

t

Close B

u

tton Inp

u

t

Stop B

u

tton Inp

u

t

Open B

u

tton

Close B

u

tton

Stop B

u

tton

A

u

xiliary Close Limit (

N

.O.) (4)

A

u

xiliary Open Limit (

N

.O.) (4)

.75

A

Maxim

u

m C

u

rren

t

D

u

ring Alarm

DC

DC

3-B

u

tton Common

Control

V

oltag

e

Control Gro

u

nd

Safety
Edge

Operator Annunciator

3-Button
Station

Auxiliary Limit
Switches

2-Wire Smoke
Detector Wiring

2-Wire Smoke
Detector Wiring
(4 Detector
Maximum)

Smoke
Detector

2.2

kOhm

Smoke
Detector

(PU) (YE)

Voice Board

Speaker - V oic e
Board Model Only

+ Speaker
- Speaker

OR

BATTERY CONNECTION / MAINTENANCE

Use two (2) 12V 4.5AH sealed
lead acid batteries in series.
Maximum charge current 1A.
Replace batteries every 2 years.

Black Wire to Black T ermina l

Battery Interconnect Wire
Battery 1 Red to Battery 2 Black

Battery 1

Battery 2

Red Wire to Red T ermina l

Power Con.
TB2

POWER CONNECTION

Hot

120Vac

1-Phase

Neutral
120Vac
1-Phase

TB2

L1 L2 L3

Replace batteries every 2 years.

Field Wiring shall consist of 22-18 AWG wiring.
Use only 250 VAC, 2 Amp, 3 AG Slo-Blo fuses.

1. Supervised, power limited circuit, 20 Ohm

maximum line impedance.

2. Unsupervised circuit, 20 Ohm maximum line

impedance.

3. Unsupervised, power limited circuit, 20 Ohm

maximum line impedance.

4. Maximum of 4 Class B Style A detectors.

LMEOLRES-2-2 required for supervision.

5. Maximum of 2 Class B Style W notification

appliances. 0.75 Amp at 24 VDC maximum.
Supervised, non-power limited circuit. 20 Ohm
maximum line impedance. Place 2.2 kOhm
resistor between 16 & 20 if unused.

LMEOLRES-2-2

(1)

(4)

(4)

(2)