Troubleshooting, Troubleshooting chart – LiftMaster RSW12V Residential / Light Commercial Swing Gate Operator with Battery Backup User Manual

Page 32

Advertising
background image

31

TROUBLESHOOTING »

TROUBLESHOOTING CHART

OPERATOR DOES NOT

RESPOND TO

COMMAND.

• Battery not connected. At least one charged battery must be connected for the operator remote control to operate. Verify battery

fuse is intact. Check battery connections and battery voltage to be above 11.5Vdc. Replace batteries if necessary.

• STOP button connection loose or disconnected. Press the RESET button and verify that the STOP LED lights up and then turns off

after 10 seconds. Verify the wire connects between the STOP and CTRL PWR terminals.

• Radio module not plugged in. Verify the green Radio module (located next to the coaxial connector) is properly mated with both

4-pin connectors.

GATE STOPS

AND REVERSES

IMMEDIATELY AFTER

IT STARTS MOVING.

• Obstruction sensed. Check safety devices and gate for obstructions.
• A fault has occurred. Check Diagnostic LED for possible error codes.
• Force set too low. Adjust FORCE setting until gate completes a full open/close cycle without reversing. The force setting may need to

be adjusted in cold weather, as the gate will not move freely.

• Loops are reversed. Make sure that the Safety loop and Shadow loop are connected properly. The gate may trigger the Shadow

loop as it moves, so it must be connected to the correct input.

• Low or defective battery. At least one charged battery must be connected for the units to operate. Verify battery fuse is intact.

Check battery connections and battery voltage to be above 11.5Vdc. Replace battery if necessary.

GATE OPENS BUT

DOES NOT CLOSE.

• An open input is continuously activated. Check the open loop or vehicle probe to make sure they are clear of objects. Verify

connections and operation for these devices.

• Low battery. Measure the voltage across the battery. Voltage should be above 11.5Vdc. Replace battery if necessary.
• (Optional Accessory) Entry system output is connected to the OPEN input, and is “stuck” opening. Verify entry system connections

and operations.

• Obstruction blocking close photoelectric sensors, shadow loop, or safety loop. Check photoelectric sensors for alignment and verify

all connections and operation for safety devices.

• (Optional Accessory) Close safety edge is damaged or on an obstruction. Verify operation and connection of close edge.

• Verify that the Timer-to-Close is ON and adjusted to desired delay.
• Gate opened by a force obstruction reversal. Check the Diagnostic LED and clear gate path of any obstructions.
• The Interrupt loop or Shadow loop is obstructed (optional accessories).
• Obstructed close photoelectric sensor or edge (optional accessory). Check connections and operations of safety devices.
• Low battery. Measure the voltage across the battery. Voltage should be above 11.5Vdc. Replace battery if necessary.

GATE DOES NOT CLOSE

AUTOMATICALLY WITH

TIMER TO CLOSE

ENABLED.

GATE 2 CLOSES

BEFORE GATE

1.

ALARM CONSTANTLY

SOUNDS 5 MINUTES.

SOUNDS WHENEVER A

COMMAND IS ISSUED.

ALARM IS BEEPING

3 TIMES ON A

COMMAND GATE

RUNS TOO SLOW.

• An open input is continuously activated. Check the open loop or vehicle probe to make sure they are clear of objects. Verify

connections and operation for these devices.

• (Optional Accessory) Entry system output is connected to the OPEN input, and is “stuck” opening. Verify entry system connections

and operation.

• Operator in Party mode after RESET button pressed while at the OPEN limit. Use a remote or the SINGLE BUTTON to close the gate

and reopen it. Verify that the TIMER RUNNING LED is flashing.

• Double entrapment occurred. Two successive obstructions were encountered while moving the gate. Press the reset button and

ensure that the gate path is clear of all obstructions. Check the FORCE setting to make sure it is properly set.

• Low battery. Measure the voltage across the battery. Voltage should be above 11.5Vdc. Replace battery if necessary.
• Open and Close Limits are set too close together. If the Open and Close Limits are set within the ramp down distance of each other,

the gate will run at slow speed all the time.

• The gate is starting within the ramp down distance from the Open or Close Limit. Gate will run slow to limits if motion is started

within the ramp-down distance from the limit.

• Lock/Bipart Delay not set. Slide the Lock/Bipart Delay switch to ON. Verify that Gate 1 starts moving first on open and last on

close.

• Gate is excessively heavy. Verify that the gate is within the ratings for this product. Disconnect the operator(s) and verify that both

gate(s) operate easily. If the gate(s) are harder to move in one direction verses the other, the gate must be adjusted.

• Gate is unbalanced. Disconnect the operator(s) and verify that gate(s) operate easily in both directions. If the gate(s) are harder to

move in one direction verses the other, the gate must be adjusted.

• Bad motor connection. Check the motor wires and connections for possible loose or corroded terminals.

ALARM BEEPS

WHEN RUNNING.

• Low battery. Measure the voltage across the battery. Voltage should be above 11.5Vdc. Replace battery if necessary.