ATRT-03, ATRT-03A, AND ATRT-03B USER’S MANUAL
REV 7
83
The screen will then be updated with the test results for each phase:
NOTE
The ratio reading should be 1.0000 ±0.1% for all tests.
Press any key to return to the “START-UP” menu.
RATIO mA % DIFF
+1.0000 0001
+1.0000 0001
+1.0000 0001
Y TO Y TEST