REV 2 CT-7000 S2 USER’S MANUAL

32

3.1.15. Configuring the Contact Filter Settings

The contact filter setting is applicable only for timing circuit breakers with insertion resistors.
Although the CT-7000 S2 automatically detects the contact time using its own algorithm, it also
allows the user to enter a custom filter value. The value can be between 1 and 300. A filter
setting of 1 allows the CT-7000 S2 to pick up the first contact transition time after the resistor
contact activity is detected. A filter setting of 300 allows the CT-7000 S2 to pick up the last
contact transition time after the resistor contact activity is detected. Use the steps below to set
the contact filter value:

a. Start from the “START-UP” menu:

Press the

[4]

key (DIAGNOSTICS).

b. The following screen will be displayed:

Press the

[4]

key (NEXT PAGE).

c. The following screen will be displayed:

Press the

[3]

key (CONTACT FILTER).

d. The following screen will be displayed:

Type the new filter value using the numeric keypad and then press the

[ENTER]

key.

The contact filter value will be set and you will be returned to the “START-UP” menu.

NOTE

The filter value will be reset to the automatic setting when the unit’s power is
cycled.

ENTER FILTER SETTING

(1 – 300)

CURRENT SETTING: 1
NEW SETTING?

1. PRINT DATA

2. ENCODER FILTER

3. CONTACT FILTER

1. SLOW CLOSE TEST

2. CHECK HOOKUP

3. TEST TRANSDUCER

4. NEXT PAGE

1. TIME BRKR 02/04/11

2. GET RSLT 09:04:05

3. SETUP

4. DIAGNOSTICS