MODEL CT-7500
OPERATING INSTRUCTIONS
24
Rev 2 Jan 2001
9.1.1 Timing an OPEN Operation With No Insertion Resistor
Table 9-1. Open Operation With No Resistor
STEP
OPERATION
ACTION
DISPLAY
1
READY TIMER FOR BREAKER OPERATION.
PRESS #1 KEY.
INSERTION RESISTOR?
1.NO
2.YES
2
SELECT NO INSERTION RESISTOR.
PRESS #1 KEY.
TIMING WINDOWS:
1.WINDOW = 1 SECOND
2.WINDOW = 10 SECONDS
3
SELECT 1-SECOND WINDOW.
PRESS #1 KEY.
1.INTERNAL TRIGGER
2.EXTERNAL TRIGGER
4
SELECT INTERNAL TRIGGER.
PRESS #1 KEY.
TIMING MODE:
1. OPEN
2. CLOSE
3. O-C
4. C-0
5. O-C-O
5
SELECT OPEN OPERATION.
PRESS KEY #1.
OPEN TIMING
Hold "ARM" Switch,
Then "START".
"STOP" to ABORT
6
INITIATE OPEN COMMAND.
HOLD "ARM" KEY AND
PRESS "START" KEY.
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
7
ANALYZER IS READY TO OUTPUT RESULTS.
NONE.
1.TIME BREAKER
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
Note
One-second timing windows are used for breaker timing; 10-second timing windows are used
for circuit-switcher timing.