EZCT VERSION 5.x SOFTWARE MANUAL

REV 1

38

5. The following screen will be displayed showing the test parameters:

Set the voltage range using the CT Tester’s “Voltage Control” knob to the voltage range
displayed in the message area, and then click on the “Start Test” button to start the test.

6. The following screen will be displayed:

Turn the CT Tester’s voltage control knob clock-wise until the CT saturates. As you turn
the knob, the voltage will be displayed under the “Data” section as shown below: