Hood troubleshooting – XLT XD-9007A (ELEC Oven Version – C, AVI Hood Version – C) User Manual

Page 16

Advertising
background image

16

Technical Support US: 888-443-2751

Technical Support INTL: 316-943-2751

HOOD TROUBLESHOOTING

Initial troubleshooting of the hood:
1. Make sure that the RUN lamp and POWER lamp on the VFD are lit.
2. Check to see that the green fan LED on the switch plate is on.
3. Check the actual frequency of the VFD controller. To access the actual frequency, press and

hold the <FUNC> button until the Display Mode shows D001. Release the button, and then
press one (1) more time. This will show actual operating parameters, not programmed parame-
ters.

4. Check to see that the breaker on the hood electrical box is not tripped.
5. Check to see that the breaker in the service panel is not tripped.
6. Make sure the Switch Relocation Cords (SRC) are properly installed to the oven(s).
7. Check to see that the grease filters are clean & installed properly.
8. Check to see if the exhaust fan is rotating in the correct rotation. To verify fan rotation, re-

move the lid on the exhaust fan. Visually inspect rotation in accordance with label on fan hous-
ing.

If the corrective actions listed above do not correct the problem, then XLT has qualified

customer service personnel that can provide assistance on any type of XLT Oven or AVI Hood
problem you may experience. Customer Service is available at 888-443-2751 24/7/365, or visit

www.xltovens.com

. The website offers an interactive troubleshooting guide that can further assist

in diagnosing problems.

The VFD has internal diagnostics, and may show the following ERROR codes:

 E01-E04 Inverter output was short circuited
 E05 motor overload is detected by electronic thermal function
 E07 DC bus voltage exceeds a threshold
 E09 DC bus voltage is below a threshold
 E14 Ground fault detected between controller output and motor


If any of the above error codes are displayed, then follow these steps to clear them.

1. Check VFD display for error code and record it.
2. Clear error by pressing the <STOP RESET> button.
3. Press the <RUN> button to activate exhaust fan.
4. Normal operation resumes with no error codes.
5. If error codes return press the <STOP RESET> button.

For repairs or maintenance of the fire suppression system and components, contact the lo-

cal Ansul dealer or XLT for assistance.