IEI Integration AUPS UART Protocal SPC User Manual
Page 8

AUPS
IEI Technology Corp.
- 8 -
Read Smart Battery Alarm (Command :
0x40
),and return 2 bytes
High byte:
Return byte
Name
Description
Bit 0
ADIN_ACTF
If 1 = DC Power is connected to AUPS module
Bit 1
BUZZER_ACTF
If 1 = Buzzer is enabled
Bit 2
UPSONOFF_ACTF
If 1 = UPS output is turned on
Bit 3
LAN_ACTF
If 1 = LAN is enabled
Bit 4
BATB_ACTF
If 1 = Battery B is connected
Bit 5
BATA_ACTF
If 1 = Battery A is connected
Bit 6
None
Don’t Care
Bit 7
None
Don’t Care
Low byte:
Return byte
Name
Description
Bit 0
BATA3_ACTF
If 1 = Battery A type is 3 packs in serial
Bit 1
BATB3_ACTF
If 1 = Battery B type is 3 packs in serial
Bit 2
BATA4_ACTF
If 1 = Battery A type is 4 packs in serial
Bit 3
BATB4_ACTF
If 1 = Battery B type is 4 packs in serial
Bit 4
BATA2_ACTF
If 1 = Battery A type is 2 packs in serial
Bit 5
BATB2_ACTF
If 1 = Battery B type is 2 packs in serial
Bit 6
SOFT_OFF
If 1 =window OS is Shut Down
Bit 7
None
Don’t Care
Note: None : Read as ‘0’