IEI Integration AUPS UART Protocal SPC User Manual

Page 8

Advertising
background image

AUPS

IEI Technology Corp.

- 8 -

Read Smart Battery Alarm (Command :

0x40

),and return 2 bytes

High byte:

Return byte

Name

Description

Bit 0

ADIN_ACTF

If 1 = DC Power is connected to AUPS module

Bit 1

BUZZER_ACTF

If 1 = Buzzer is enabled

Bit 2

UPSONOFF_ACTF

If 1 = UPS output is turned on

Bit 3

LAN_ACTF

If 1 = LAN is enabled

Bit 4

BATB_ACTF

If 1 = Battery B is connected

Bit 5

BATA_ACTF

If 1 = Battery A is connected

Bit 6

None

Don’t Care

Bit 7

None

Don’t Care

Low byte:

Return byte

Name

Description

Bit 0

BATA3_ACTF

If 1 = Battery A type is 3 packs in serial

Bit 1

BATB3_ACTF

If 1 = Battery B type is 3 packs in serial

Bit 2

BATA4_ACTF

If 1 = Battery A type is 4 packs in serial

Bit 3

BATB4_ACTF

If 1 = Battery B type is 4 packs in serial

Bit 4

BATA2_ACTF

If 1 = Battery A type is 2 packs in serial

Bit 5

BATB2_ACTF

If 1 = Battery B type is 2 packs in serial

Bit 6

SOFT_OFF

If 1 =window OS is Shut Down

Bit 7

None

Don’t Care

Note: None : Read as ‘0’