IEI Integration AUPS UART Protocal SPC User Manual

Page 9

Advertising
background image

AUPS

IEI Technology Corp.

- 9 -


Read Smart Battery Status (Command :

0x41

),and return 2 bytes

High byte:

Return byte

Name

Description

Bit 0

TEMPOVER_A

If 1 = Battery A is not charging , temperature > 60

ºC

Bit 1

TEMPOVER_B

If 1 = Battery B is not charging, temperature > 60

ºC

Bit 2

TEMPGOVER_A

If 1 = Battery A is charging, temperature > 45

ºC

Bit 3

TEMPGOVER_B

If 1 = Battery B is charging, temperature > 45

ºC

Bit 4

VOLOW_A

If 1 = Battery A Output Voltage < normal rated voltage

Bit 5

VOLOW_B

If 1 = Battery B Output Voltage < normal rated voltage

Bit 6

VOLOVER_A

If 1 = Battery A Output Voltage > normal rated voltage

Bit 7

VOLOVER_B

If 1 = Battery B Output Voltage > normal rated voltage

Low byte:

Return byte

Name

Description

Bit 0

BATTERYFULL_A

If 1 = Battery A Full

Bit 1

BATTERYFULL_B

If 1 = Battery B Full

Bit 2

BATA_CHGF

If 1 = Battery A is charging

Bit 3

BATB_CHGF

If 1 = Battery B is charging

Bit 4

BATA_STANDBY

If 1 = Battery A is standby

Bit 5

BATB_STANDBY

If 1 = Battery B is standby

Bit 6

BATA_USE

If 1 = Battery A is discharging

Bit 7

BATB_USE

If 1 = Battery B is discharging






























Advertising