Installation, Warning – Lincoln Electric IM10103 AIR VANTAGE 700 (AU) User Manual
Page 17

A-7
INSTALLATION
AIR VANTAGE
®
700 (Au) CuMMINS
A-7
• Only a licensed, certified, trained electrician
should install the machine to a premises or resi-
dential electrical system. be certain that:
• The installation complies with the National
Electrical Code and all other applicable electri-
cal codes.
• The premises is isolated and no feedback into
the utility system can occur. Certain laws require
the premises to be isolated before the generator
is linked to the premises. Check your local
requirements.
------------------------------------------------------------------------
2. Take necessary steps to assure load is limited to
the capacity of the AIR VANTAGE
®
700 (AU) CUM-
MINS by installing a 32 amp, 415 VAC three pole
circuit breaker. Loading above the rated output will
reduce output voltage below the allowable -10% of
rated voltage which may damage appliances or
other motor-driven equipment and may result in
overheating of the AIR VANTAGE
®
700 (AU) CUM-
MINS engine.
3. Install a 32 amp 3 phase plug to the triple-pole cir-
cuit breaker using 6.02mm (minimum) x 4 conductor
cable of the desired length.(1 x 32 amp / 415 V & 2
x 15 amp / 240 V, plugs are available in the optional
KA1373-2 plug kit).
4. Plug this cable into the 3 phase receptacle on the
AIR VANTAGE
®
700 (AU) CUMMINS case front.