AuXILIARY POWER OPERATION
Start the engine and set the IDLER control switch to
the desired operating mode. Full power is available
regardless of the welding control settings, if no weld-
ing current is being drawn.
SIMuLTANEOuS WELDING AND AuXIL-
IARY POWER LOADS
It must be noted that the above auxiliary power ratings
are with no welding load.
Simultaneous welding and power loads are specified
in table B.5.
AIR VANTAGE
®
700 (Au) CuMMINS Extension Cord Length
Recommendations
(Use the shortest length extension cord possible sized per the following table.)
AIR VANTAGE
®
700 (Au) CuMMINS
b-11
OPERATION
b-11
TAbLE b.5 AIR VANTAGE
®
700 (Au) CuMMINS SIMuLTANEOuS WELDING AND POWER LOADS
Maximum Allowable Cord Length in m (ft.) for Conductor Size
Conductor size is based on maximum 2.0% voltage drop.
2.5
2
mm 14AWG 4.0
2
mm 12AWG 6.0
2
mm 10AWG 10.0
2
mm 8AWG 16.0
2
mm 6AWG 25.0
2
mm 4AWG
Load
(Watts)
3,600
Current
(Amps)
15
Voltage
(Volts)
240
18
(60)
23
(75)
46
(150)
69
(225)
107
(350)
183
(600)
WELD
AMPS
0
100
200
300
400
500
600
1 PhASE
WATTS
AMPS
7,200 30
7,200 30
7,200 30
7,200 30
7,200 30
6,400 26
0 0
3 PhASE
WATTS
AMPS
20,000 28
20,000 28
20,000 28
16,800 23
12,000 16
6,400 9
0 0
bOTh 1 AND 3 PhASE
WATTS
AMPS
------
28
------
28
------
28
------ 23
7,200 ------
6,400 ------
0 ------
PLuS
OR
OR