AuXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to
the desired operating mode. Full power is available
regardless of the welding control settings, if no weld-
ing current is being drawn.

SIMuLTANEOuS WELDING AND AuXIL-
IARY POWER LOADS

It must be noted that the above auxiliary power ratings
are with no welding load.

Simultaneous welding and power loads are specified
in table B.5.

AIR VANTAGE

®

700 (Au) CuMMINS Extension Cord Length

Recommendations

(Use the shortest length extension cord possible sized per the following table.)

AIR VANTAGE

®

700 (Au) CuMMINS

b-11

OPERATION

b-11

TAbLE b.5 AIR VANTAGE

®

700 (Au) CuMMINS SIMuLTANEOuS WELDING AND POWER LOADS

Maximum Allowable Cord Length in m (ft.) for Conductor Size

Conductor size is based on maximum 2.0% voltage drop.

2.5

2

mm 14AWG 4.0

2

mm 12AWG 6.0

2

mm 10AWG 10.0

2

mm 8AWG 16.0

2

mm 6AWG 25.0

2

mm 4AWG

Load

(Watts)

3,600

Current

(Amps)

15

Voltage

(Volts)

240

18

(60)

23

(75)

46

(150)

69

(225)

107

(350)

183

(600)

WELD

AMPS

0

100
200
300
400
500
600

1 PhASE

WATTS

AMPS

7,200 30
7,200 30
7,200 30
7,200 30
7,200 30

6,400 26

0 0

3 PhASE

WATTS

AMPS

20,000 28
20,000 28
20,000 28
16,800 23
12,000 16

6,400 9

0 0

bOTh 1 AND 3 PhASE

WATTS

AMPS

------

28

------

28

------

28

------ 23
7,200 ------
6,400 ------

0 ------

PLuS