Maple Systems HMI5000 Series User Manual
Page 10

10
HMI5000 Series Installation Guide
1010-1005 Rev 05 www.maplesystems.com
b. Strip about ¼” of insulation from the black and red wires.
c. Connect the red wire to the 24V DC positive (+) input of the
HMI power terminal block.
d. Connect the black wire to the 24V DC negative (–) input of
the HMI power terminal block.
e. Connect the power cable shield wire to the HMI power
terminal block’s chassis ground input.
2. Route the power cable to the HMI power supply. The power
cable should not be any longer than necessary.
3. Install the power supply wires as follows (with colors shown for
Maple Systems cable P/N 6030-0009):
Color
Power Supply
HMI
Red
+Output/+24V DC
+24 V
Black
–Output/+24V DC return
GND
Shield
Case ground
FG or
NOTE: The power connector on the HMI5000 Series uses a 3-position
terminal block with screw-down clamps. Lugs are not required.
Panel Preparation
A metal panel or mounting surface with a minimum thickness of 15
gauge (0.059 in/3.3 mm) if cold-rolled steel or hardened steel, or 10
gauge (0.101 in/2.6 mm) if aluminum alloy (6061-T6 preferred) is
required. Thinner panels or surfaces may bow between the mounting
clamps and not form a seal with the gasket. Make sure all supplied
mounting clamps are used and that the panel does not flex or bow more
than 0.010 in. to ensure a proper seal.
The HMI should be mounted into a panel with a depth of at least 4 in.
(105 mm). Allow a clearance of at least 1 in. (25 mm) on each side for