Maple Systems HMI5000 Series User Manual
Page 14

14
HMI5000 Series Installation Guide
1010-1005 Rev 05 www.maplesystems.com
Maintenance
Figure 6: DIP switch positions (power must be cycled on the HMI to enable the DIP
switch mode except DIP switch 4).
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Calibration mode (except X-models)
OFF
ON
OFF
OFF
Hide System Toolbar
OFF
OFF
ON
OFF
Force into Boot Loader mode
OFF
OFF
OFF
ON
Power Button Enable (X-models only)
OFF
OFF
OFF
OFF
Normal operation
Touchscreen Calibration mode: This mode allows you to recalibrate
the touchscreen. Note: Calibration mode is accessed through the HMI’s
System Toolbar on the X-models.
Hide System Toolbar: Hides the arrow in the bottom-right corner of the
screen that accesses the System Toolbar (same as “Hide System Toolbar”
in System Parameters and LB9020).
Boot Loader mode: This mode forces the HMI to not execute the
project. This mode is used when replacing or reinstalling the operating
system. Contact Maple Systems for more information.
Power Button Enable (X-models only): Enable (ON) or disable (Off)
the front panel Power button.
Fusing Requirements
If the display does not come on within two seconds of power up, remove
power. An internal fuse will prevent damage if the polarity of the DC
power is incorrect. Check wiring to insure proper connections and try to
power up again.