Attachment method – Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual

Page 6

Advertising
background image

6

‹RS-422

Unit's Connector

: XM3B-0942-132L<made by OMRON>

Recommended Connector

: XM2A-0901

<made by OMRON>

Recommended Cover

: XM2S-0913

<made by OMRON>

Jack Screw

: XM2Z-0073

<made by OMRON>

Stacking Metal Fittings require #4-40 inch screw.

Attachment Method

• For the GP-4200 series, attach the unit to the panel.

„ Attaching the Unit directly to the Display

When attaching the unit on the rear side of the Display, among the 4 screws shown in the diagram
below, use 2 horizontally positioned or 2 vertically positioned screws to attach the unit. If the
Display already has an attachment, it may restrict the direction in which you can place the unit.

Pin Arrangement

Pin #

RS-422

Signal Name

Direction

Meaning

1

TRMRX

-

Termination
(Receive side: 100

Ω)

2

RDA

Input

Receive Data A(+)

3

SDA

Output

Send Data A (+)

4

NC

-

No connection

5

SG

-

Signal Ground

6

VCC

-

+5V

±

5% output 0.05A

*1

*1

The VCC output for Pin #6 is not protected against overcurrent. To prevent
damage or unit malfunctions, use only the rated current.

7

RDB

Input

Receive Data B(-)

8

SDB

Output

Send Data B(-)

9

TRMTX

-

Termination (Send side: 100

Ω)

Shell

FG

-

Frame Ground

5

1

6

9

75[2.95]

75[2.95]

EXT*