GP-4100 Series Hardware Manual
4-8
Power Cord Specifications
Power Connector Specifications
Connecting the Power Cord
(1)
Confirm that the GP unit’s Power Cord is unplugged from the power supply.
(2)
Use a flat-blade screwdriver (Size 0.4 x 2.5) to loosen the terminal screws.
(3)
Strip the power cord, and attach it to the power connector.
Power Cord Diameter
Simple Wire: 0.75 to 1.5mm
2
Stranded Wire: 0.75 to 1mm
2
(18 - 16 AWG)
Conductor Type
Simple or Twisted Wire
Conductor Length
• Use copper conductors only.
• If the Conductor’s end (individual) wires are not twisted correctly, the end wires may
either short against each other, or against an electrode.
+
24V
-
0V
FG
FG Grounding Terminal connected to
the GP
•
The power supply connector is MKDS 1/3-3,81 (made by Phoenix Contact).
• To avoid an electric shock, prior to connecting the GP unit’s power cord terminals to
the power terminal block, confirm that the GP unit's power supply is completely
turned OFF, via a breaker, or similar unit.
• The temperature rating of field installed Conductors:75°C only.
5mm
[0.2 in.]
+
-
FG
GP Rear