GP-4100 Series Hardware Manual

4-10

„Power Cord Specifications

„Power Connector (Plug) Specifications

WARNING

HAZARD OF ELECTRIC SHOCK

• Prior to connecting the GP unit's power cord terminals to the power terminal block, confirm that the GP

unit's power supply is completely turned OFF, via a breaker, or similar unit.

• Supplying a power voltage other than that specified will damage the power source and the GP unit.

• Since there is no power switch on the GP unit, be sure to attach a breaker-type switch to its power cord.

• When the FG terminal is connected, be sure the wire is grounded.

Failure to follow these instructions will result in death or serious injury.

• When the FG terminal is connected, be sure the wire is grounded. Not grounding the

GP unit will result in excess noise and vibration.

• The SG and FG terminals are connected internally in the GP unit.

When connecting the SG wire to another device, be sure that the design of the

system/connection does not produce a shorting loop.

Power Cord Diameter

0.75 to 1.5mm

2

(18-16AWG)

Conductor Type

Simple or Twisted Wire

Conductor Length

• Use copper conductors only.

• If the Conductor’s end (individual) wires are not twisted correctly, the end wires may

either short against each other, or against an electrode.

+

24V

-

0V

FG

FG Grounding Terminal connected to the
GP

7mm
[0.3in.]

Insertion
Direction

+
-

FG