27

Command: K5PQRC

Response: K5P200CRLF

loop 5 proportional gain is 200

To set the integral multiplier:

T(1)M(a)CR

T is the time indicator

1 affects all loops

M indicates the multiplier

a is the value from 1 to 3

Command affects all loops.

The integral multiplier sets the range and resolution of the integration time. Values can
be input according to the following table with corresponding resolution:

Multiplier Range Resolution
1 0 to 255 sec 1 sec
2 0 to 510 sec 2 sec
3 0 to 765 sec 3 sec
4 0 to 1020 sec 4 sec

Example:

Command: T1M3CR sets integral multiplier to 3 for all loops

Response: T1M3CRLF

Note: Changing the integral multiplier after setting the integration time will cause
the integration time to change.

To query the integral multiplier:

T(1)MQCR

To set the integration (reset) time:

T(n)I(abcd)CR

T is the time indicator
n is the loop number
I is the integral indicator
abcd is the value from 0000 to 1020 sec

The integration range depends on the integral multiplier, see above. [abcd must be
divisible by the integral multiplier]

To query the integration time:

T(n)IQCR