1.1.1 ALARM MODE I/O LINE CONFIGURATION
The alarm mode input and output designations are as follows:

I/O Line Nr.

Input/Output

Designation

00

Output

Loop 1 High Alarm

01

Output

Loop 2 High Alarm

02

Output

Loop 3High Alarm

03

Output

Loop 4 High Alarm

04

Output

Loop 5 High Alarm

05

Output

Loop 6 High Alarm

06

Output

Loop 7 High Alarm

07

Output

Loop 8 High Alarm

08

Output

Loop 1 Low Alarm

09

Output

Loop 2 Low Alarm

10

Output

Loop 3 Low Alarm

11

Output

Loop 4 Low Alarm

12

Output

Loop 5 Low Alarm

13

Output

Loop 6 Low Alarm

14

Output

Loop 7 Low Alarm

15

Output

Loop 8 Low Alarm

16

Input

User Designated

17

Input

User Designated

18

Input

User Designated

19

Input

User Designated

20

Input

User Designated

21

Input

User Designated

1.1.2 ALARM DEADBAND

To prevent oscillating of the alarm output when the measured temperature hovers
around the alarm setpoint, a deadband may be specified. The deadband is defined as
a percentage of the setpoint for all 16 alarm settings.

For high alarms, the alarm output will be set when the measured temperature reaches
the high alarm setpoint but will not be cleared until the temperature drops below its
lower deadband limit.

For low alarms, the alarm output will be set when the measured temperature drops
below the low alarm setpoint and will not be cleared until the temperature rises
above its upper deadband limit.