Communication baud rate, Communication protocol, Ac line frequency – Watlow 8LS Controller User Manual
Page 59: Comm baud? 96, Comm ptcl? ana, Ac line? 60 hz

Setup
8LS User’s Guide 51
Communication Baud Rate
Use this menu to set the communications baud rate.
Selectable values: 2400 or 9600.
NOTE
If you are using ANASOFT, be sure to set ANAIN-
STL to the same baud rate you set in this menu.
Communication Protocol
Use this menu to set the protocol type to either Allen Bradley or
ANAFAZE.
Selectable values: ANA (ANAFAZE) or A/B (Allen Bradley).
AC Line Frequency
Use this menu to configure the controller to match the AC line
frequency. Since the controller reduces the effect of normal mode noise
by integrating the signal over the period of the AC line frequency, that
accuracy will be reduced if this is not set correctly.
Selectable values: 60 Hz or 50 Hz.
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
COMM
BAUD? 96
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
COMM
PTCL? ANA
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
AC LINE?
60 HZ