High process alarm setpoint, High process alarm status, High process alarm output number – Watlow 8LS Controller User Manual
Page 77: 1 alarms hp? off, 1 hi pro outpn = 0

Setup
8LS User’s Guide 69
High Process Alarm Setpoint
Use this menu to select the setpoint at which the high process alarm
activates. The high process alarm activates when the process variable
(PV) goes above the high process setpoint. It deactivates when the PV
goes below the high process setpoint minus the deadband value, if you
have set one.
Selectable values: Any point within the scaled sensor range.
High Process Alarm Status
Use this menu to enable or disable the high process alarm.
Selectable values: On, Off.
High Process Alarm Output Number
Use this menu to assign the digital output that activates when the loop is
in high process alarm.
Selectable values: 0-30.