Specifications (cont.), Ordering part number – Watlow EZ-ZONE PM Express Limit User Manual
Page 32

EZ-ZONE PM Limit Express
• 32 •
Specifications
Specifications (cont.)
Output Hardware
• Switched dc
- 22 to 32VÎ(dc) @ 30mA
• Open collector, maximum sink current 100 mA, @ 30VÎ(dc)
• Electromechanical relay, Form C, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load, 100,000 cycles at
rated load
• Electromechanical relay, Form A, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load, 100,000 cycles at
rated load
Operator Interface
• Dual 4 digit, 7 segment LED displays
• Typical display update rate 1Hz
• Advance, RESET, up and down keys plus an EZ-Key/s (not available in 1/32 DIN)
Ordering Part Number
(Part number digits 1 through 14)
PMXLXXX-AAAABXX
All Models include: *Universal Sensor Input, Standard Bus Configuration Communications
*Dual line Red over Green 7 Segment displays
Package Size (Digit #3)
3 = 1/32 DIN
6 = 1/16 DIN
8 = 1/8 DIN vertical
9 = 1/8 DIN horizontal
4 = 1/4 DIN
Primary Function (Digit #4)
L = Limit Controller w/ Universal Input
Power Supply (Digit #5)
1 = 100-240 VAC
3 = 12-28 VAC/DC
Output 1 and 2 Hardware Options (Digits #6 and #7)
Output 1
Output 2
AJ = None
Mechanical relay 5A, Form A
CJ = Switched dc/open collector
Mechanical relay 5A, Form A
EJ = Mechanical Relay 5 Amp form C
Mechanical relay 5A, Form A
Future Options (Digits #8 thru #11)
AAAA = None
Menu Type (Digits #12)
B = Express
Additional Options (Digits #13 and #14)
AA = Standard EZ-ZONE face plate
AB = EZ-ZONE logo and no Watlow name
AC = No logo and no Watlow name