Specifications (cont.), Ordering part number – Watlow EZ-ZONE PM Express Limit User Manual

Page 32

Advertising
background image

EZ-ZONE PM Limit Express

• 32 •

Specifications

Specifications (cont.)

Output Hardware

• Switched dc

- 22 to 32VÎ(dc) @ 30mA

• Open collector, maximum sink current 100 mA, @ 30VÎ(dc)

• Electromechanical relay, Form C, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load, 100,000 cycles at

rated load

• Electromechanical relay, Form A, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load, 100,000 cycles at

rated load

Operator Interface

• Dual 4 digit, 7 segment LED displays

• Typical display update rate 1Hz

• Advance, RESET, up and down keys plus an EZ-Key/s (not available in 1/32 DIN)

Ordering Part Number

(Part number digits 1 through 14)

PMXLXXX-AAAABXX

All Models include: *Universal Sensor Input, Standard Bus Configuration Communications

*Dual line Red over Green 7 Segment displays
Package Size (Digit #3)

3 = 1/32 DIN

6 = 1/16 DIN

8 = 1/8 DIN vertical

9 = 1/8 DIN horizontal

4 = 1/4 DIN
Primary Function (Digit #4)

L = Limit Controller w/ Universal Input
Power Supply (Digit #5)

1 = 100-240 VAC

3 = 12-28 VAC/DC
Output 1 and 2 Hardware Options (Digits #6 and #7)

Output 1

Output 2

AJ = None

Mechanical relay 5A, Form A

CJ = Switched dc/open collector

Mechanical relay 5A, Form A

EJ = Mechanical Relay 5 Amp form C

Mechanical relay 5A, Form A

Future Options (Digits #8 thru #11)

AAAA = None
Menu Type (Digits #12)
B = Express
Additional Options (Digits #13 and #14)
AA = Standard EZ-ZONE face plate
AB = EZ-ZONE logo and no Watlow name