Watlow EZ-ZONE RMH User Manual

Page 66

Advertising
background image

Watlow EZ-ZONE

®

RMH Module

63

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[FAiL]
[FAiL]

Control Loop (1 to 16)

Input Error Failure

Select what the controller

outputs will do when an

input error switches control

to manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless transfer

maintains same output

power, if it was less than

75% and stable, otherwise

0% (14)

[MAn]

Manual power sets

output power to Manual

Power setting (33)

[USEr]

User sets output pow-

er to last open-loop set point

the user entered (100)

User

5244
[offset 80]

0x6B

(107)

1 to 16

0xD (13)

- - - -

7013

uint

RWES

[MAn]
[MAn]

Control Loop (1 to 16)

Manual Power

Set the manual output

power level that will take

effect if an input error fail-

ure occurs while User Fail-

ure Action is set to Manual

Power.

Set Point Open Loop Limit

Low to Set Point Open Loop

Limit High (Setup Page)

0.0

5240
[offset 80]

0x6B

(107)

1 to 16

0xB (11)

- - - -

7011

float

RWES

[`L;dE]
[ L.dE]

Control Loop (1 to 16)

Open Loop Detect En-

able

Turn on the open-loop

detect feature to monitor

a closed-loop operation for

the appropriate response.

[``no]

No (59)

[`YES}

Yes (106)

No

4142
[offset 70]

0x97 (151)

1 to 16

0x16 (22)

64

8039

uint

RWES

[`L;dt]
[ L.dt]

Control Loop (1 to 16)

Open Loop Detect Time

The Open Loop Detect De-

viation value must occur

for this time period to trig-

ger an open-loop error.

0 to 3,600 seconds

240

4144
[offset 70]

0x97 (151)

1 to 16

0x17 (23)

65

8040

uint

RWES

[`L;dd]
[ L.dd]

Control Loop (1 to 16)

Open Loop Detect Devia-

tion

The value entered repre-

sents the Process Value de-

viation that must occur to

trigger an open-loop error.

-1,999.000 to 9,999.000°F or

units

-1,110.555 to 5,555.000°C

10.0°F or

units

6.0°C

4146
[offset 70]

0x97 (151)

1 to 16

0x18 (24)

66

8041

float

RWES

[``rP]

[ rP]

Control Loop (1 to 16)

Ramp Action

Select when the controller's

set point will ramp to the

defined end set point.

[`oFF]

Off (62)

[`Str]

Startup (88)

[StPt]

Set Point Change

(1647)

[both]

Both (13)

Off

5246
[offset 80]

0x6B

(107)

1 to 16

0xE (14)

- - - -

7014

uint

RWES

[`r;SC]

[ r.SC]

Control Loop (1 to 16)

Ramp Scale

Select the scale of the ramp

rate.

[hoUr]

Hours (39)

[Min]

Minutes (57)

Minutes

5248
[offset 80]

0x6B

(107)

1 to 16

0xF (15)

- - - -

7015

uint

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set

Advertising