Watlow EZ-ZONE

®

RMH Module

78

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`S2;A]
[ SZ.A]

Counter (1 to 24)

Source Zone A

Set the zone of the function

selected above.

0 to 16

0

12228

[offset 40]

0x82 (130)

1 to 24

5

- - - -

30005

uint
RWES

[sas;A]
[SAS.A]

Counter (1 to 24)

Source Active State A

Set what output state will

indicate on.

[high]

High (37)

[LoW]

Low (53)

[both]

Both (130)

High

12240

[offset 40]

0x82 (130)

1 to 24

0x0B (11)

- - - -

30011

uint
RWES

[SFn;B]
[SFn.b]

Counter (1 to 24)

Source Function B

Set the type of function

that will be used for the

counter load signal.

[nonE]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[`lgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

12222

[offset 40]

0x82 (130)

1 to 24

2

- - - -

30002

uint
RWES

[`Si;B]
[ Si.b]

Counter (1 to 24)

Source Instance B

Set the instance of the

function selected above.

1 to 250

1

12226

[offset 40]

0x82 (130)

1 to 24

4

- - - -

30004

uint
RWES

[`S2;B]
[ SZ.b]

Counter (1 to 24)

Source Zone B

Set the zone of the function

selected above.

0 to 16

0

12230

[offset 40]

0x82 (130)

1 to 24

6

- - - -

30006

uint
RWES

[sas;b]
[SAS.b]

Counter (1 to 24)

Source Active State B

Set what output state will

indicate on.

[high]

High (37)

[LoW]

Low (53)

High

12242

[offset 40]

0x82 (130)

1 to 24

0xC (12)

- - - -

30012

uint
RWES

[LoAd]
[LoAd]

Counter (1 to 24)

Load Value

Set the counter's initial

value.

0 to 9,999

0

12244

[offset 40]

0x82 (130)

1 to 24

(13)

157

30013

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User