How to Use Data Communications

17

WATLOW Series 733/734

Command Summary Series 733/734 Data Communications

Name

Description

Read (?) and/or Write (=) Syntax

Range

(data.1)

Add ETX & STX with ANSI X3.28 Protocol

(data.2)

A1HI

Zone 1 Alarm High

? <sp> A1HI <cr>

Process Alarm: A1LO to R1H

= <sp> A1HI <sp> data.2 <cr>

Deviation Alarm:
0 to 555°C/0 to 999°F

A1LO

Zone 1 Alarm Low

? <sp> A1LO <cr>

Process Alarm: R1L to A1HI

= <sp> A1LO <sp> data.2 <cr>

Deviation Alarm:
0 to -555°C/0 to -999°F

A2HI

Zone 2 Alarm High

? <sp> A2HI <cr>

Process Alarm: A2LO to R2H

= <sp> A2HI <sp> data.2 <cr>

Deviation Alarm:
0 to 555°C/0 to 999°F or Units

A2LO

Zone 2 Alarm Low

? <sp> A2LO <cr>

Process Alarm: R2L to A2HI

= <sp> A2LO <sp> data.2 <cr>

Deviation Alarm:
0 to -555°C/0 to -999°F or Units

AL1

Zone 1 Alarm Type

? <sp> AL1 <cr>

0 = Process Alarm

= <sp> AL1 <sp> data.2 <cr>

1 = Deviation Alarm
2 = No Alarm

AL2

Zone 2 Alarm Type

? <sp> AL2 <cr>

0 = Process Alarm

= <sp> AL2 <sp> data.2 <cr>

1 = Deviation Alarm
2 = No Alarm

ALM

Alarm Status

? <sp> ALM <cr>

0 = No alarms occurring

(Writing a 0 will clear

= <sp> ALM <sp> 0 <cr>

1 = A1HI occurring

all alarms if all alarm

2 = A1LO occurring

conditions no longer

4 = A2HI occurring

exist.)

8 = A2LO occurring

AUT1

Zone 1 Auto-tune

? <sp> AUT1 <cr>

0 = No auto-tuning

= <sp> AUT1 <sp> data.2 <cr>

1 = Slow response tuning
2 = Medium response tuning
3 = Fast response tuning

AUT2

Zone 2 Auto-tune

? <sp> AUT2 <cr>

0 = No auto-tuning

= <sp> AUT2 <sp> data.2 <cr>

1 = Slow response tuning
2 = Medium response tuning
3 = Fast response tuning

C1

Zone 1 Process Value ? <sp> C1 <cr>

Between R1L and R1H

C2

Zone 2 Process Value ? <sp> C2 <cr>

Between R2L and R2H

CAL1

Zone 1 Cal Offset

? <sp> CAL1 <cr>

-99°F to 99°F

= <sp> CAL1 <sp> data.2 <cr>

-55°C to 55°C

CAL2

Zone 2 Cal Offset

? <sp> CAL2 <cr>

-99°F to 99°F

= <sp> CAL2 <sp> data.2 <cr>

-55°C to 55°C
-99 Units to 99 Units

CF

Degrees Select

? <sp> CF <cr>

0 = Display °F

= <sp> CF <sp> data.2 <cr>

1 = Display °C

CSP

Current Set Point

? <sp> CSP <sp> zone <cr>

0 = Zone 1
1 = Zone 2

CT1

Zone 1 Cycle Time

? <sp> CT1 <cr>

1 to 60 seconds

= <sp> CT1 <sp> data.2 <cr>

CT2

Zone 2 Cycle Time

? <sp> CT2 <cr>

1 to 60 seconds

= <sp> CT2 <sp> data.2 <cr>

Table continued on the next page.

Commands

Table 5 -
Command Summary
with Read (?) and
Write (=) Simple
Syntax and Data
Range/Responses.