Input 1 wiring, Thermocouple, Rtd (2- or 3-wire) 100platinum – Watlow Series 97 User Manual

Page 16: Input 2 wiring, Digital event, Input 1, Input 2, Figure 3.6a, Figure 3.6b, Figure 3.6c

Advertising
background image

3 . 6

W i r i n g

Wa t l o w S e r i e s 9 7

Input 1 Wiring

Figure 3.6a

– Thermocouple

Available on all units

Impedance: 20M

Figure 3.6b

– RTD (2- or 3-Wire) 100

Platinum

Available on all units

Input 2 Wiring

Figure 3.6c –

Digital Event

97 _ 1 - _ _ _ _ - _ _ _ _

Voltage input

3-36VÎ (dc) Event Input High State

0-2VÎ (dc) Event Input Low State

Contact closure

0-2k

Event Input Low State

> 23k

Event Input High State

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

3

1

+

-

2.67k

EVENT

+

3

EVENT

-

1

20k

100

+5V

1

2

3

4

5

6

7

1

5

6

7

S1

S2

S3

3-wire

1

2

3

4

5

6

7

6

7

S1

S3

5

2-wire

jumper 5 to 6

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

- 6

+7

NOTE:

Successful installation
requires five steps:

• Choose the controller’s

hardware configuration
and model number
(Appendix);

• Choose a sensor

(Chapters 3 and 6, and
Appendix);

• Install the controller

(Chapter 2);

• Wire the controller

(Chapter 3) and

• Configure the controller

(Chapters 4, 5 and 6).

ç

WARNING:

To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to
install and operate the
Series 97. Failure to do
so could result in such
damage, and/or injury or
death.

ç

CAUTION:

Maintain isolation
between input 1 and
input 2 to prevent a
ground loop. A ground
loop may cause incorrect
readings, dashes across
the upper display or the
display of error codes.
Failure to follow this
guideline could result in
damage to equipment
and product.