Operation Parameters

Set Point 2: Sets the operating set point for Output 2 when control mode is Ht/

Ht or CL/CL. SP2 only appears when Ot1 and 0t2 are the same, and functions

as an ON/OFF control.

Proportional Band: Set the proportional bandwidth for each Output, adjustable

from 0

°

to 999°F or 0 to 555°C for ranges displayed in whole degrees, and 0 to

99.9°F or 0 to 55.5°C for ranges displayed in 0.1°. If set at Pb = 0, the Series
9801985 functions as a simple ON/OFF control with a 3°F or 1.7°C switching
differential for ranges displayed in whole degrees, and 0.3°F or 0.17°C for

ranges displayed in 0.1°. The default is 25°F/13°C.

If the input type is 0-5VDC or 4-20mA, the range of Pb1 is 0-999, 0-99.9 or O-

9.99 (determined by the value of DEC). The switching differential is 0.03, 0.3 or

3 units. Pb2 default is 0. Pb2 only appears with Ht/CL or CL/Ht operation.

Reset: Enter Reset for Output 1 or 2, adjustable from 0.00 to 9.99 rpts/min. A

value of 2.00 rpts/min. corresponds to an integral time constant of 30 seconds.

Selecting 0.00 = no integral action. rE2 only appears with Ht/CL or CL/Ht

operation. rA X will not appear if Pb X = 0 respectively.

Rate: Adjust Rate function for Output 1 or 2, from 0.00 to 9.99 minutes maxi-
mum. Selecting 0.00 = no derivative action. rA2 will only appear with Ht/CL or
CL/Ht operation. rA X will not appear if Pb X = 0 respectively.

Cycle Time: Enter the Cycle Time for each Output, adjustable from 1 to 60

seconds. The default will be 5 seconds. Ct1 will not appear if Output 1 is 4-20.

CT2 only appears with Ht/CL or CL/Ht operation..

Figure 29 -

The Operation Menu.