Watlow Series F4P User Manual

Page 11

Advertising
background image

Wa t l o w S e r i e s F 4 P

O p e r a t i n g f r o m t h e F r o n t P a n e l

2 . 5

• Return to factory for evaluation.

• Component failure.

Upper

[Atod`]

Lower !Timeout x
(x is 1 to 3)

• Repair or replace sensor.
• Reverse sensor wiring connections.

Red lead is usually negative for tc.

• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and

3 are not isolated from each other.

• Sensor open.
• Sensor wired backwards. Display

decreases as process increases.

• Input type set to wrong sensor.
• Ground loop

Upper

[SEnhi]

Lower !Input Sensor x+
(x is 1 to 3)

• Repair or replace sensor.
• Reverse sensor wiring connections.

Red lead is usually negative for tc.

• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and

3 are not isolated from each other.

• Sensor shorted (RTD).
• Sensor wired backwards. Display

decreases as process increases.

• Input type set to wrong sensor.
• Ground loop

Upper

[SEnLo]

Lower !Input Sensor x-
(x is 1 to 3)

• Repair or replace sensor.
• Reverse sensor wiring connections.

Red lead is usually negative for tc.

• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and

3 are not isolated from each other.

• Sensor open.
• Sensor wired backwards. Display

decreases as process increases.

• Input type set to wrong sensor.
• Ground loop

Upper

[A-dhi]

Lower !Input x AtoD+
(x is 1 to 3)

• Repair or replace sensor.
• Reverse sensor wiring connections.

Red lead is usually negative for tc.

• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and

3 are not isolated from each other.

• Sensor shorted (RTD).
• Sensor wired backwards. Display

decreases as process increases.

• Input type set to wrong sensor.
• Ground loop

Upper

[A-dLO]

Lower !Input x AtoD
(x is 1 to 3)

Input Errors
(Upper Display shows error code

for input 1 only. Lower Display
shows additional errors. Input
2 and 3 error messages appear
in Lower Display. Alarm
Output Indicator is lit.)

• Tune PID set.
• Check power limit settings.
• Replace fuse or reset circuit breaker.

• Reposition sensor to accurately mea-

sure process.

• Check slidewire settings.

• PID values set incorrectly.
• Power limit set incorrectly.
• Open fuse or circuit breaker on energy

source.

• Incorrect sensor location in the pro-

cess.

• Slidewire (if used) settings incorrect.

• Process will not reach set

point.

• Check operation mode. Automatic is

closed loop, manual is open loop.

• Check power limit settings.
• Check sensor, repair or replace.
• Check outputs, repair or replace.
• Check output settings.
• Check system wiring.

• Controller in manual operation mode

(percent power).

• Power limit set incorrectly.
• Thermocouple shorted.
• Shorted power switching device.
• Output set incorrectly (heat vs. cool).
• System wired incorrectly.

• Process runs away (too high or

too low).

• Check power limit settings.
• Tune PID set.
• Use correct PID set.

• Power limit set incorrectly.
• PID values set incorrectly.
• Incorrect PID set active.

Controllability
• Process will not

stabilize.

• Check alarm logic setting and output

wiring.

• Alarm logic setting incorrect or output

wired incorrectly.

• Alarm output action is

reversed.

Corrective Action

Probable Cause(s)

Indication