Watlow Series F4P User Manual

Page 97

Advertising
background image

1

PID Set 1

2

PID Set 2

3

PID Set 3

4

PID Set 4

5

PID Set 5

307

Autotune PID Type, Autotune PID

r/w

0

Heat Only,

1

Cool Only

2

Heat and Cool

304

Autotune Set Point, System

r/w

50 to 150%

884

Boost Delay Time, Control Set Points

r/w

0 to 999 seconds

881

Boost Power Mode, Control Output 1B

r/w

0

Auto Only

1

Auto/Manual

883

Boost Power, Control Set Points

r/w

0 to 1000% (in tenths)

309

Boost Set Point (1B), Control Set Points

r/w

-19999 to 30000 [deviation]
Set Point Low Limit to Set Point High Limit [process]

882

Boost Set Point Type, Control Output 1B

r/w

0

Process

1

Deviation

885

Boost Type, Control Output 1B

r/w

0

Boost on Power

1

Boost on Set Point

1603

Calibrate Input 1, Calibration

r/w

1

0.00mV Thermocouple

2

50.00mV Thermocouple

3

32°F Type J

4

Ground

5

Lead

6

15.0 ohms RTD

7

380.0 ohms RTD

8

0.000V

9

10.000V

10 4.000mA
11 20.000mA

1608

Calibrate Input 2, Calibration

r/w

1

0.00mV Thermocouple

2

50.00mV Thermocouple

3

32°F Type J

4

Ground

5

Lead

6

15.0 ohms RTD

7

380.0 ohms RTD

8

0.000V

9

10.000V

10 4.000mA
11 20.000mA

1613

Calibrate Input 3, Calibration

r/w

1

0.00mV Thermocouple

2

50.00mV Thermocouple

3

32°F Type J

4

Ground

5

Lead

6

15.0 ohms RTD

7

380.0 ohms RTD

8

0.000V

9

10.000V

10 4.000mA
11 20.000mA
12 15.0 ohms Slidewire (F4P_-_ _ AB-_ _ _ _ models only)
13 1000.0 ohms Slidewire (F4P_-_ _ AB-_ _ _ _ models only)

1606

Calibrate Process Output 1A, 1.000V

r/w

0 to 3000V (in thousandths)

1607

Calibrate Process Output 1A, 10.000V

r/w

0 to 12000V (in thousandths)

1605

Calibrate Process Output 1A, 20.000mA

r/w

0 to 24000mA (in thousandths)

1604

Calibrate Process Output 1A, 4.000mA

r/w

0 to 6000mA (in thousandths)

1611

Calibrate Process Output 1B, 1.000V

r/w

0 to 3000V (in thousandths)

1612

Calibrate Process Output 1B, 10.000V

r/w

0 to 12000V (in thousandths)

1610

Calibrate Process Output 1B, 20.000mA

r/w

0 to 24000mA (in thousandths)

1609

Calibrate Process Output 1B, 4.000mA

r/w

0 to 6000mA (in thousandths)

1626

Calibrate Retransmit Output 1, 1.000V

r/w

0 to 3000V (in thousandths)

1627

Calibrate Retransmit Output 1, 10.000V

r/w

0 to 12000V (in thousandths)

1625

Calibrate Retransmit Output 1, 20.000mA

r/w

0 to 24000mA (in thousandths)

1624

Calibrate Retransmit Output 1, 4.000mA

r/w

0 to 6000mA (in thousandths)

1631

Calibrate Retransmit Output 2, 1.000V

r/w

0 to 3000V (in thousandths)

1632

Calibrate Retransmit Output 2, 10.000V

r/w

0 to 12000V (in thousandths)

1630

Calibrate Retransmit Output 2, 20.000mA

r/w

0 to 24000mA (in thousandths)

1629

Calibrate Retransmit Output 2, 4.000mA

r/w

0 to 6000mA (in thousandths)

605

Calibration Offset Value, Analog Input 1

r/w

Set Point Low Limit to Set Point High Limit

615

Calibration Offset Value, Analog Input 2

r/w

Set Point Low Limit to Set Point High Limit

625

Calibration Offset Value, Analog Input 3

r/w

Set Point Low Limit to Set Point High Limit

1927

Cascade High Deviation, Analog Input 3

r/w

1 to 9999

1927

Cascade High Range, Analog Input 3

r/w

<sensor range>

305

Cascade Inner Loop, Autotune PID Set

r/w

0

Tune Off

1

PID Set 1

2

PID Set 2

3

PID Set 3

4

PID Set 4

5

PID Set 5

1922

Cascade Internal Set Point

r

1926

Cascade Low Deviation, Analog Input 3

r/w

-19999 to -1

1926

Cascade Low Range, Analog Input 3

r/w

<sensor range>

1925

Cascade, Analog Input 3

r/w

0

Process Cascade

1

Deviation Cascade

343

Cascade Outer Loop, Autotune PID Set

r/w

0

Tune Off

1

PID Set 1

2

PID Set 2

3

PID Set 3

4

PID Set 4

5

PID Set 5

1501

CJC1 AtoD, Diagnostic

r

HHHH

see In 1 AD

1500

CJC1 Temp, Diagnostic

r

xx.x

1532

CJC2-CJC3 AtoD, Diagnostic

r

HHHH

see In 1 AD

1531

CJC2-CJC3 Temp, Diagnostic

r

xx.x

312

Clear Alarm 1, Key Press Simulation

w

write any value

331

Clear Alarm 2, Key Press Simulation

w

write any value

311

Clear Error Input 1, Key Press Simulation

Wa t l o w S e r i e s F 4 P

C o m m u n i c a t i o n s

9 . 3

NOTE:
For more infor-

mation about

parameters, see

the Index.

Advertising