C h a p t e r 2 : I n s t a l l a n d W i r e
■
1 2
■
Wa t l o w S e r i e s N 7
Ó
Warning: Use National Electric (NEC) or other country-spe-
cific standard wiring and safety practices when wiring and
connecting this controller to a power source and to electri-
cal sensors or peripheral devices. Failure to do so may
result in damage to equipment and property, and/or injury
or loss of life.
Note:
To prevent ground loops, maintain isolation from input to
output when using switched dc or analog process outputs.
Use ungrounded thermocouples.
Process Inputs
• Voltage: 0 to 10VÎ (dc)
• Current: 0 to 20 mA
• Voltage input impedance: 50 k
Ω
• Current input impedance: 100
Ω