Process outputs, Figure 13b — process output 2, Figure 13a — process output 1 – Watlow series l rev g - 02-12-08.pdf User Manual
Page 13: Current, Volts
Wa t l o w S e r i e s N 7
■
1 3
■
C h a p t e r 2 : I n s t a l l a n d W i r e
Ó
Warning: Use National Electric (NEC) or other country-spe-
cific standard wiring and safety practices when wiring and
connecting this controller to a power source and to electri-
cal sensors or peripheral devices. Failure to do so may
result in damage to equipment and property, and/or injury
or loss of life.
Note:
To prevent ground loops, maintain isolation from input to
output when using switched dc or analog process outputs.
Use ungrounded thermocouples.
1
2
3
4
5
6
7
8
9
10
11
12 13
14
11
10
+
–
Figure 13b — Process Output 2
1
2
3
4
5
6
7
8
9
10
11
12 13
14
4
3
–
+
Figure 13a — Process Output 1
14 pins
Control Outputs 3 & 4
Process Outputs 1 & 2
Event Inputs 5 to 8
Process Outputs
Current
• 0 to 20 mA at 20V maximum
• Load: 1 k
Ω
maximum
Volts
• 0 to 10VÎ (dc) at 20 mA maximum
• Load: 500
Ω
minimum