Setup page parameter table, System – Watlow Series F4S/D User Manual

Page 55

Advertising
background image

Wa t l o w S e r i e s F 4 S / D

S e t u p

5 . 7

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set, Ch)

Parameters to Appear

NOTE:
For more information about how parameter settings affect the con-

troller’s operation, see the Features Chapter.

Active: Always.

1206 r/w

Continue (0)

Continue (0)

Hold (1)

Terminate (2)

Reset (3)

Idle Set Point 1 (4)

Idle Set Point 2 (5)

Power-Out Action

Choose controller re-

sponse to power out-

age while running a

profile.

1213 r/w

10 seconds

(10)

0 to 30000 seconds

(0 to 30000)

Power-Out Time

Define a power out-

age in seconds.

Channel

904

[1]

907

[2]

r/w

Off (0)

Off (0)

On (1)

Open Loop Channel x (1 or 2)

Select whether to

turn off outputs and

display an error

message.

Active: Always (1).

Active if controller is Dual

Channel (2).

Fail

903

[1]

906

[2]

r/w

0% (0)

0 to 100% Heat only

0 to 100% Cool only

-100% to +100%

Cool/Heat or

Heat/Cool

Input x Fail (1 or 2)

Enter percent of

power supplied to

the output if analog

input sensor fails.

Active: Always (1).

Active if controller is Dual

Channel (2).

Point

304

[1]

323

[2]

r/w

90% (90)

50 to 150% (50 to 150)

Channel x Autotune Set

Point (1 or 2)
Set percent of set

point to auto-tune to.

Active: Always.

1923 r/w

Yes, Upper

Display (1)

No, Upper Display (0)

Yes, Upper Display (1)

Show °F or °C

Choose whether to

display or hide °C or

°F in top display.

Active: Always.

901 r/w

°F (0)

°F (0)

°C (1)

°F or °C

Choose temperature

scale.

Active: Always.

900 r/w

U S (Reset/

Rate) (0)

U S (Reset/Rate) (0)

SI (Integral/Derivative)

(1)

PID Units

Choose units for PID

control.

Active: Always.

Time

1919 [mm]

1920 [dd]

1921 [yy]

r/w

current date

M/D/Y

01/01/1998 to

12/31/2035

[mm] (1 to 12)

[dd] (1 to 31)

[yy] (1998 to 2035)

Current Date

Enter actual date.

Active: Always.

Time

1916 [hh]

1917 [mm]

1918 [ss]

r/w

current time

hh:mm:ss

00:00:00 to 23:59:59

[hh] (0 to 23)

[mm] (0 to 59)

[ss] (0 to 59)

Current Time

Enter actual time.

(24-hour-clock)

Active: Always (1).

Active if controller is Dual Chan-

nel (2).

Band

1205

[1]

1212

[2]

r/w

1

Decimal choice

dependent:

1 to 30000, or

.1 to 3000.0, or

.01 to 300.0, or

.001 to 30.0

(1 to 30000)

Guarantee Soak Band

x (1 or 2)
Select value above

and below set point

to define the soak

band.

Main > Setup > System