7 . 1 8
■
C o m m u n i c a t i o n s
Wa t l o w S e r i e s F 4 S / D
*Profiles without custom-written names are referred to by
their numbers (Profile 1, Profile 2, etc.),
Create Profile
Write Modbus Register
4002=1
Set File Number
Write Modbus Register
4000=1 to 40
-Optional-
Rename Profile*
Registers 3500 thru 3899
Insert Step
Write Modbus Register
4002=2
Set Current Step Number
Write Modbus Register
4001=1 to 256
Set Step Number to where
the "End" step is located
Write Modbus Register
4001=1 to 255
Step Type
"Autostart"?
Done with
profile?
Step Type
"Time"?
Step Type
"Rate"?
Step Type
"Soak"?
Step Type
"Jump"?
No
No
No
No
Yes
Yes
Yes
Yes
Yes
See "Autostart"
Step Type sheet
for options
See "Time"
Step Type sheet
for options
See "Rate"
Step Type sheet
for options
See "Soak"
Step Type sheet
for options
See "Jump"
Step Type sheet
for options
Assumes file does not exist
Use 1 to 40
File will be placed at lowest
empty file location.
See "End"
Step Type sheet
for options
No
Yes
Done
F4 Modbus Applications: Creating a Profile