Chapter 5: setup page – Watlow Series SD PID Profiling Controller User Manual

Page 28

Advertising
background image

Wa t l o w S e r i e s S D

2 6

C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus in

parenthesis.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[`SEn]
[ SEn]

Sensor Type

Set the analog sensor type.

[``tc] (0)
[`rtd] (1)
[`MA] (2)
[uolt] (3)
[~mu] (5)

[``tc] (0)

70 R/W

Always active.

[`Lin]
[ Lin]

Thermocouple Linearization

Set the analog input thermo-
couple linearization.

[```J] J (0) [```D] D (6)

[```H] K (1) [Pt11] PTII (7)

[```t] T (2) [```R] R (8)

[```E] E (3) [```S] S (9)

[```n] N (4) [```B] B (10)

[```C] C (5)

[tc`J] (0)

71 R/W

[`Sen] is set to [``tc].

[`C-F]
[ C-F]

Temperature Units

Set the temperature units for
thermocouple and RTD inputs.

[```F] Fahrenheit (0)
[```C] Celsius (1)

[```F] (0)

40 R/W

[`Sen] is set to [``tc]
or

[`rtd].

Temperature Units via Serial
Comms

Fahrenheit (0)

Celsius (1)

(0)

18 R/W

[`Sen] is set to [``tc]
or

[`rtd].

[S;deC]
[S.dEC]

Temperature Decimal Places

Set the decimal places for the
displayed input value for ther-
mocouple and RTD types.

[```0] (0)
[``0;0] (1)

[```0] (0)

41 R/W

[`Sen] is set to [``tc]
or

[`rtd].

[P;dEC]
[P.dEC]

Process Decimal Places

Set the decimal places for the
displayed input value for process
types.

[```0] (0)
[``0;0] (1)
[`0;00] (2)
[0;000] (3)

[```0] (0)

42 R/W

[`Sen] is set to [`mA],
[uoLt] or [`mu].

[IS;En]
[IS.En]

INFOSENSE™

Enable the sensor feature, which
synchronizes the controller with
a Watlow sensor.

[``no] (0)
[`Yes] (1)

[``no] (0)

91 R/W

Always active.

[IS;P1]
[IS.P1]

INFOSENSE™ 1

Set sensor point 1 code.

0 to 999 (0 to 999)

500

92 R/W

[IS;En] is set to [`yes].

[IS;P2]
[IS.P2]

INFOSENSE™ 2

Set sensor point 2 code.

0 to 999 (0 to 999)

500

93 R/W

[IS;En] is set to [`yes].

[IS;P3]
[IS.P3]

INFOSENSE™ 3

Set sensor point 3 code.

0 to 999 (0 to 999)

500

94 R/W

[IS;En] is set to [`yes].

[IS;P4]
[IS.P4]

INFOSENSE™ 4

Set sensor point 4 code.

0 to 999 (0 to 999)

500

95 R/W

[IS;En] is set to [`yes].

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).

5

Chapter 5: Setup Page

To go to the Setup Page, press both the Up ¿ and Down ¯ keys for three seconds from the Home Page. [`SEt]

will appear in the upper display and

[PAgE] will appear in the lower display.

• Press the Advance Key ‰ to move through the parameter prompts.

• Press the Up ¿ or Down ¯ key to change the parameter value.

• Press the Infinity Key ˆ at any time to return to the Home Page display.