Watlow Series SD31 PID with Optional Countdown Timer User Manual

Page 28

Advertising
background image

Wa t l o w S e r i e s S D 3 1

26

C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.

[PSH2]
[PSH2]

Output Power Scale High 2

Set the high end of the range within
which the output will scale.

0.0 to 100.0%

100.0%

[Ot`2] is set to [hEAt]
or

[CooL], [Ctr2] is set

to

[`Ftb] and Output 2

is not a communications
output.
(not SD_ _ - _ _ U _ -

_ _ _ _ )

[nLF2]
[nLF2]

Output Nonlinear Function 2

Select a nonlinear output curve to match
the response of your system.

[`OFF] off
[Cru1] curve 1
[Cru2] curve 2

[`OFF]

[Ot`2] is set to [hEAt]
or

[CooL].

[ti;F2]
[ti.F2]

Output Timer Function 2

Select the states for a timer output during
the timing sequence.

[dL;On] Delay On
[dL;OF] Delay Off
[S9;On] Signal On
[S9;OF] Signal Off

[dL;OF]
Delay Off

Timer model only,
SD31-XXXX-XTXX.
[`Ot2] is set to [tim].

[S;M2]
[S.M2]

Signal Time Minutes 2

Set the time in minutes for which an out-
put will go to its signal state after the
countdown completes.

0 to 99
minutes

0

Timer model only,
SD31-XXXX-XTXX.
[`Ot2] is set to [tim].

[`S;S2]
[ S.S2]

Signal Time Seconds 2

Set the low end of the range within which
the output will scale.

0 to 59
seconds

0

Timer model only,
SD31-XXXX-XTXX.
[`Ot2] is set to [tim].

[hyS1]
[hyS1]

Alarm 1 Hysteresis

Set the hysteresis for an alarm. This de-
termines how far into the safe region the
input needs to move before the alarm can
be cleared.

0.0 to 999.0
(0000 to 999000)

1.0

*106, 107
R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[Lgc1]
[Lgc1]

Alarm 1 Logic

Select the alarm output condition in the
alarm state.

[AL`C] closed on alarm (0)
[AL`O] open on alarm (1)

[AL`C] (0)

164 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[LAt1]
[LAt1]

Alarm 1 Latching

Turn alarm latching on or off.

[nLAt] off (0)
[`LAt] on (1)

[nLAt] (0)

108 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[SiL1]
[SiL1]

Alarm 1 Silencing

Turn alarm silencing on or off.

[`OFF] off (0) - no silencing
[``On] on (1) - silencing

[`OFF] (0)

109 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[dSP1]
[dSP1]

Alarm 1 Message

Displays an alarm message when an
alarm is active.

[`OFF] off (0) - no message
[``On] on (1) - message

[``On] (1)

110 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[hyS2]
[hyS2]

Alarm 2 Hysteresis

Set the hysteresis for an alarm. This de-
termines how far into the safe region the
input needs to move before the alarm can
be cleared.

0.0 to 999.0

1.0

[Ot`2] is set to [dE;AL]
or

[Pr;AL].