2. HART COMMUNICATOR OPERATION

(10) Integral Indicator Scale

T0204.EPS

Display

Mode

Display

Related

Parameters

NORMAL %

USER SET

USER & %

INP PRES

PRES & %

% rnge 45.6%

Description

Engr disp range

20.0M

% rnge

45.6%

Engr disp range

20.0M

Pres 456 kPa

% rnge 45.6%

Pres 456 kPa

Indicates –5 to
110% range
depending on the
set range (LRV,
URV).

Indicates user set
and % alternately
in 3 second
intervals.

Indicates input
pressure.

Indicates input
pressure and %
alternately in 3
second intervals.

Displays values
depending on
engr disp LRV
and engr disp
URV Units set
using engr disp
unit are not
indicated.

* The number of lines displayed on the LCD is determined by the

number of LRV and URV lines set on the brain terminal.

See (a) through (c) for each setting procedure.

% indication and input
pressure indication

Normal %
Input press
Input press & %

User-set engineering
unit display

User set
User set & %

Engr disp unit

Engr disp LRV

Engr disp URV

F0221.EPS

Transmitter is set
for “NORMAL %”
when shipped.

For % display, set
this parameter
only.

Set for user-set
engineering unit
display.

Set a unit to be
displayed on
the HART Com-
munication.

Set a numeric
value for engi-
neering unit for
4 mA output
(LRV).

Set a numeric
value for engi-
neering unit for
20 mA output
(HRV).

(a) Display Mode

Follow the instructions given to the below to
change the range of integral indication scale.
When

USER SET

is selected, the user set values

of integral indication.

F0222.EPS

(ENTER)

EJA:
Display mode
Normal %
Normal %
User set
User set & %
Input press

HELP

SEND

ESC

ENTER

Select User set and press ENTER
(F4)
.
Press SEND (F2) to send the data
to the transmitter.

(SEND)

1. Device setup

4. Detailed setup

4. Display condition

1. Display mode

Example: Set the integral indicator scale to engineering units

display

(b) Setting User-set Engineering Unit

Engr unit

allows entry of the engineering units to

be displayed on the HART communicator. When
the instrument is shipped, this is set as specified in
the order. Follow the procedure below to change
this setting.
Since these units are not displayed on the integral
indicator, use the adhesive labels provided

Engr

unit

need not be set for % display.

F0223.EPS

(ENTER)

EJA:
Engr unit

HELP

DEL

ESC

ENTER

Set M, and press ENTER (F4).

(SEND)

1. Device setup

4. Detailed setup

4. Display condition

3. Engr disp range

1. Engr unit

Example: Set an engineering unit M.

(c) Lower and Upper Range Value Setup in

Engineering Unit

Engr disp LRV

and

Engr disp URV

are used to

set the lower and higher range values for the
engineering unit display. When the instrument is
shipped, these are set as specified in the order.
Note that these items need not be set for % display.