Yokogawa EJA115 User Manual

Page 22

Advertising
background image

IM 01C22T01-01E

2-15

2. HART COMMUNICATOR OPERATION

6

F0231.EPS

Because the reading on the
ammeter is 4.000 mA, select YES
and press ENTER (F4).
If the reading is not 4.000 mA,
select item 2. NO. Repeat steps
and until the ammeter reads
4.000 mA.

EJA:
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No

HELP

SET

ABORT

ENTER

EJA:
Setting fld dev
output to 20mA

DEL

SET

ABORT

OK

7

4

4

5

5

Press OK (F4), and the transmitter
outputs the output signal of 100%.

EJA:
Enter meter value

20.000

HELP

DEL

ABORT

ENTER

8

Carry out the same procedures as
those described under and .

EJA:
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No

HELP

ABORT

9

Returning fld dev to original
output
appears.

DEL

ENTER

(OK)

(ENTER)

(ENTER)

‘1 9.0 5 0‘

EJA:
NOTE-Loop may be
returned to automatic
control

HELP

ESC

10

Press OK (F4).

DEL

OK

(OK)

(ENTER)

Ammeter reading: 19.050

Ammeter reading: 20.000

Ammeter reading: 4.000

1

F0232.EPS

Select the Scaled D/A trim item.

EJA:
Trim analog output
1 D/A trim
2 Scaled D/A trim

HELP

SET

HOME

OK

EJA:
WARN-Loop should be
removed from
automatic control

DEL

SET

ABORT

OK

2

Press OK (F4).

EJA:
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change

HELP

DEL

ABORT

ENTER

3

Select Change, and press ENTER
(F4)
.
The same operations as for D/A
trim
are required when selecting
item 3. Proceed.

EJA:
Set scale- Lo output
value
4
4

HELP

ABORT

4

Enter the value read on the meter
when the signal is 4 mA. In this
case, Enter the value of the voltage
across a 250

resistor (1 V), and

press ENTER (F4).

DEL

ENTER

(OK)

(ENTER)

‘1’

EJA:
Set scale- Hi output
value
20
20

HELP

ABORT

5

Enter the value read on the meter
when the signal is 20 mA. Then,
enter 5, and press ENTER (F4).

DEL

ENTER

(ENTER)

‘5’

Example 2: To adjust using a voltmeter

6

Select Proceed and press ENTER
(F4)
.

EJA:
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change

HELP

SET

ABORT

ENTER

EJA:
Connect reference
meter

DEL

SET

ABORT

OK

7

Connect the voltmeter, and press
OK (F4).

EJA:
Setting fld dev
output to 4mA

HELP

DEL

ABORT

OK

8

Press OK (F4). The output signal of
0% is output.

(OK)

(OK)

(ENTER)