2. HART COMMUNICATOR OPERATION

2.3 Parameters

2.3.1 Parameter Usage and Selection

Before describing the procedure for setting parameters,
we present the following table showing how the
prameters are used and in what case.

NOTE

Do not turn off the transmitter as soon as HART
Communicator settings (sending) have been
made. If the transmitter is turned of less than 30
seconds after parameters have been set, the set
data will not be stored and the terminal returns
to previous settings.

Table 2.3.1 Parameter Usage and Selection

Memory

Transmitter

Display

HART output

Monitoring

Maintenance

Adjustment

T0201.EPS

Item

HART Communicator

Description

Page

Tag

Descriptor

Message

Date

Unit

LRV/URV

Apply values

Xfer fnctn

Damp

Low cut

Cut mode

Bi-dire mode

H

2

O Unit select

Snsr temp unit

Static pres unit

Display fnctn

Display mode

Engr disp range

Burst option

Burst mode

Poll addr

Auto poll

Pres

% rnge

A01 out

Snsr temp

Static pres

Engr display

Loop test

Self test

Status

A01 Alarm typ

Ext SW mode

Write protect

Enable write

New password

Zero trim

Lower/Upper sensor trim

D/A trim, Scaled D/A trim

Tag number, Up to 8 characters

Up to 16 characters

Up to 32 characters

xx/yy/zz

Set the calibration range by the keypad

Range for 4 to 20 mA DC signal is set with actual input applied.

Linear or Zero

Used to measure bi-directional flows.

at 4

°

C (39.2

°

F)/at 20

°

C (68

°

F)

Sets a unit for temperature displayed on the model 275.

Sets a unit for static pressure displayed on the model 275.

Engr unit/Engr disp LRV/Engr disp URV/Engr disp point.

Selection of the data to be sent continuously (Pres/% rnge/A01 out).

ON/OFF switching of burst mode.

Setting the polling address (1 to 15).

ON/OFF switching of multi-drop mode.

Pressure variable

% output variable

4 to 20 mA output variable

Sensor temperature

Static pressure

Displays output as on an LCD. settable in the engr disp range.

Display of the result of self-test, calibration of transmitter.

Display the status of 4 to 20 mA DC output when a failure

Display/set the external volume protect/permit for LRV (URV) setting.

Setting a new password.

Set the current input value to 0 kPa.

Adjust only measured pressure variable.

Adjust the output value at the points of 4 mA and 20 mA.

Engineering unit

Range

Output mode

Damping time constant

Output signal low cut
mode

Bi-direction flow
measurement mode

H

2

O unit selection

Unit for displayed
temperature

Unit for displayed static
pressure

Integral indicator display
mode

Integral indicator scale

Burst mode

Multi-drop mode

Test output

Self-diagnostics

Output when CPU error
has occurred

External volume
protect/permit

Software Write Protect

Zeroing

Sensor trim

Analog output trim

inH

2

O, inHG, ftH

2

O, mmH

2

O, mmHG, psi, bar, mbar, g/cm

2

, kg/cm

2

, Pa, kPa, MPa, torr, atm

Sets mode for output signal to “linear mode” (proportional to input differential pressure)
or to “Square root mode” (proportional to flow).

Adjust the output response speed for 4 to 20 mA DC. 0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32
(sec)

Used mainly to stabilize output near 0 if output signal is the square root mode. Two
mode are available: forcing output to 0% for input below a specific value, or changing to
proportional output for input below a specific value.

Sets mode for integral indicator to “linear mode” (proportional to input differential
pressure) or to “Square root mode” (proportional to flow).

Set the following 5 types of integral indicator scale ranges and unit: “% scale indicator”,
“use set scale indicator”, “alternate indication of user set scale and % scale”, “input
pressure display” and “alternate indication of input pressure and % scale.

Used for loop checks. Output can be set freely from –5% to 110% in 1% step.

Check using the self-test command. If an error is detected, the corresponding message
is displayed.

Displays the permit/protect status of setting changes depending on communications.

Write protect status is released for 10 minutes when the password is entered.

P.2-7

P.2-8

P.2-9

P.2-10

P.2-19

P.2-12

P.2-10

P.2-10

P.2-16

P.2-11

P.2-12

P.2-13

P.2-14

P.2-19

P.1-2

P.2-17