2. HART COMMUNICATOR OPERATION

2.3.3 Setting Parameters

(1) Tag No.

To change the Tag No., see section 2.2.4 Entering,
Setting, and Sending Data.

Up to 8 characters can be set with

Tag

. The maximum

number of characters to be set for other items is as
shown below. With Option code /CA, the Descriptor is
filled in at the factory as specified in the order.

Item

The Number of Characters

Tag
Descriptor
Message
Date

8

16
32

2/2/2

T0202.EPS

1. Device setup

3. Basic setup

1. Tag

F0210.EPS

EJA:YOKOGAWA
Tag
YOKOGAWA
YOKOGAWA

HELP

DEL

ESC

ENTER

Example: To change from Tag YOKOGAWA to FIC-1A.

Call up the

Tag

setting display.

See Section 2.2.4.

(2) Unit

The unit is set at the factory before shipment if
specified at the time of order. Follow the procedure
below to change the unit.

1

F0211.EPS

Press Hot key and call up Range
values
.

EJA:
Hot Key
1 Keypad input
2 Enable Write
3 New Password

DEL

SET

ESC

ENTER

EJA:
keypad input
1 LRV 0.00 mmH2O
2 URV 3000.00 mmH2O
3 Unit mmH2O
4 LSL -3500 mmH2O
5 USL -3500 mmH2O

HELP

SAVE

HOME

ENTER

2

Select the Press Unit item to set
the units of pressure.

EJA:
Pressure unit
mmH2O
mmH2O
mmHg
psi
bar

DEL

SAVE

ESC

ENTER

3

Select the desired engineering unit
and press ENTER (F4).

HELP

×

3

(ENTER)

Example: To change the unit from mmH

2

O to inH

2

O

F02111.EPS

EJA:
keypad input
1 LRV 0.00 mmH2O
2 URV 3000.00 mmH2O
3 Unit inH2O
4 LSL -3500 mmH2O
5 USL 3500 mmH2O

DEL

ESC

4

Press SEND (F2) to send the new
unit to the transmitter memory.

HELP

SEND

ENTER

(SEND)

EJA:
keypad input
1 LRV 0.00 inH2O
2 URV 118.000 inH2O
3 Unit inH2O
4 LSL -140.0 inH2O
5 USL 140.0 inH2O

DEL

ESC

5

Check that disappears.

HELP

SEND

ENTER

SEND

(3) Range Change

Ranges are factory-set as specified by the customer.
To rerange, change the settings as follows:

(a) Keypad — LRV, URV

1

F0212.EPS

Select the 4. LRV item.

EJA:
Online
1 Device setup
2 Pres
3 A01 Out
4 LRV
5 URV

DEL

SET

ESC

ENTER

EJA:
1 LRV 0.0 mmH2O
2 URV 2500 mmH2O

HELP

SAVE

HOME

ENTER

2

To set the Lower Range Valve,
select the LRV item.

EJA:
LRV
0.0 mmH2O
0.0

HELP

DEL

ESC

ENTER

3

Enter 500, and press ENTER (F4).

EJA:
1 LRV 500 mmH2O
2 URV 3000.0 mmH2O

DEL

HOME

4

To change the Upper Range Valve,
select the URV item.

HELP

SEND

ENTER

(ENTER)

‘3 5 0 0’

(ENTER)

‘5 0 0’

(SEND)

EJA:
URV
2500.0 mmH2O
2500.0

HELP

ESC

5

Enter 3500, and press ENTER (F4).

DEL

ENTER

EJA:
1 LRV 500.0 mmH2O
2 URV 3500.0 mmH2O

HELP

HOME

6

Press SEND (F2) to send the
changed data to the transmitter.
Check that disappears.

SEND

ENTER

SEND

Example: To change the range from 0 to 2500 mmH

2

O to

500 to 3500 mmH

2

O