4) output mode (linear/sq root), Output mode (linear/sq root) -8, Call up the apply values display – Yokogawa EJA115 User Manual

Page 15: Call up the xfer fnctn display

Advertising
background image

IM 01C22T01-01E

2-8

2. HART COMMUNICATOR OPERATION

NOTE

It is possible to set LRV

Ͼ

URV. This setting

reverses the 4 to 20 mA output signal.
Conditions:

LSL

Յ

LRV

Յ

USL

LSL

Յ

URV

Յ

USL

|URV

Ϫ

LRV|

Ն

Min. Span

The 4 to 20 mA output does not correspond to
the scale of the indicator under the following
conditions in which;
• the equipment with standard specification is

used with the setting changed to the above
setting.

• the customer specified equipment (with the

above factory-setting) is used with the setting
changed to the normal (standard) setting.

In the cases above, replace the scale with one
which corresponds correctly to the 4 to 20 mA.

(b) Changing the Ranges While Applying an

Actual Input — Apply values

This feature allows the lower and upper range values to
be setup automatically with the actual input applied. If
the upper and lower range values are set, “

URV

” and

LRV

” are changed at the same time.

The measurement span is determined by the upper and
lower range valves. Changing the lower range value
results in the upper range value change automatically,
keeping the span constant.

1

F0213.EPS

Press OK (F4).

Call up the

Apply Values

display.

EJA:
WARN-Loop should be
removed from
automatic control

DEL

SET

ABORT

OK

EJA:
Set the:
1 4mA
2 20mA
3 Exit

HELP

SAVE

ABORT

ENTER

2

To set the lower range value, select
4mA and press ENTER (F4).

EJA:
Apply new 4ma input

HELP

DEL

ABORT

OK

3

Apply the pressure of 500mmH

2

O.

After obtaining a stable pressure,
press OK (F4).

(ENTER)

(OK)

(OK)

1. Device setup

3. Basic setup

3. Re-range

2. Apply values

Example: To change the range from 0 to 2500 mmH

2

O to

500 to 3000 mmH

2

O

F02131.EPS

EJA:
Current applied
process value:
500.01 mmH2O
1 Set as 4mA value
2 Read new value
3 Leave as found

DEL

ABORT

4

The LRV to be changed is 500.01
mmH

2

O.

• Selecting item 1 sets LRV to

500.01 mmH

2

O.

• Selecting item 2 reads LRV again.
To set LRV = 500.01, select item 1
and press ENTER (F4).

HELP

SEND

ENTER

(ENTER)

EJA:
Set the
1 4mA
2 20mA
3 Exit

HELP

ABORT

5

Select Exit and press ENTER (F4).
Check the value after completing
the range change with URV and
LRV.
* The span is maintained the same

as when changing LRV with Apply
values
. In this case, if LRV is
changed from 0 to 500, URV is
changed automatically to 3000.

DEL

ENTER

×

2

(ENTER)

(4) Output Mode (Linear/Sq root)

The output mode has already been set to a Linear
output (

Linear

). Follow the procedure below to

change the mode.

1

F0214.EPS

Call up the

Xfer fnctn

display.

EJA:
Transfer function
Linear
Linear
Sq root

DEL

SET

ESC

ENTER

[1] Select Sq root, and press

ENTER (F4).

[2] Press SEND (F2) to send the

data to the transmitter, then
check to confirm that
disappears.

(ENTER)

1. Device setup

3. Basic setup

5. Xfer fnctn

(SEND)

SEND

Example: To change the mode from Linear to Sq root.

The output mode is set as specified in the order when
the instrument is shipped.

If the instrument is equipped with an integral indicator
and Transfer function is sq root, “

” is displayed on

the integral indicator.